61
Instruction Manual
CVM-C4
Digital inputs
Quantity
2
Type
Potential free contact
Insulation
3.5kV rms
Maximum short-circuit current
4 mA
Maximum voltage in open circuit
30V
Impulse outputs
Type
Passive pulse
Maximum voltage
27 V
Maximum current
27 mA
Maximum frequency
10 Hz
Minimum pulse width
80 mA
RS-485 Communications
Communications protocol
Modbus RTU
Baud rate
2400 - 4800 - 9600 - 19200 bps
Data bits
8
Stop bits
1 - 2
Parity
without, even, odd
User interface
Display
LCD
Keyboard
3 keys
Environmental Features
Operating temperature
-10ºC ... +60ºC
Storage temperature
-20ºC ... +70ºC
Relative humidity (without condensation)
5... 95%
Maximum altitude
2000 m
Protection degree
Front: IP54, Rear: IP20
Pollution degree
2
Mechanical characteristics
Terminals
1, 2, 4... 9, 11...17, 47...50, 58, 59, 70 ... 72
2.5 mm
2
0.5 Nm
Flat (SZS 0.6x3.5)
Dimensions
(mm)
Weight
265 g.
Enclosure
pc + abs
Standards
Electromagnetic compatibility (EMC) Part 4-2: Testing and measurement techniques� Elec-
trostatic discharge immunity test�
IEC 61000-4-2
Electromagnetic compatibility (EMC) Part 4-3: Testing and measurement techniques� Ra-
diated, radio-frequency, electromagnetic field immunity test�
IEC 61000-4-3
Electromagnetic compatibility (EMC) Part 4-4: Testing and measurement techniques� Elec-
trical fast transient/burst immunity test�
IEC 61000-4-4
Electromagnetic compatibility (EMC) Part 4-5: Testing and measurement techniques�
Surge immunity test�
IEC 61000-4-5
Electromagnetic compatibility (EMC) Part 4-6: Testing and measurement techniques� Im-
munity to conducted disturbances, induced by radio-frequency fields�
IEC 61000-4-6
Содержание CVM-C4 Series
Страница 1: ...Power analyzer CVM C4 INSTRUCTION MANUAL M267B01 03 21C...
Страница 2: ...2 CVM C4 Instruction Manual...
Страница 64: ...64 CVM C4 Instruction Manual 11 CE CERTIFICATE...
Страница 65: ...65 Instruction Manual CVM C4...
Страница 66: ...66 CVM C4 Instruction Manual...