42
CVM-C4
Instruction Manual
6�3�3�- ALARM PARAMETER
Note:
Visible variable if the relay operating mode has been configured as an alarm output.
This screen is used to configure the parameter on which the alarm will be activated.
do-1
itEn
Un H
>3s
do-1
itEn
Un H
-
.
.
With a long keystroke (>3s), press
to access the value's configuration.
Use the keys
and
to browse through the different options:
Un. H
, Active alarm when the Phase - Neutral voltage is higher than the alarm value
Un. L
, Active alarm when the Phase - Neutral voltage is lower than the alarm value
UL. H
, Active alarm when the Phase - Phase voltage is higher than the alarm value
UL. L
, Active alarm when the Phase - Phase voltage is lower than the alarm value
i. H
,
, Active alarm when the current is higher than the alarm value
i. L
, Active alarm when the current is lower than the alarm value
P. H
, Active alarm when the total active power is higher than the alarm value.
P. L
, Active alarm when the total active power is lower than the alarm value
q. H
, Active alarm when the total reactive power is higher than the alarm value.
q. L
, Active alarm when the total reactive power is lower than the alarm value.
S. H
, Active alarm when the total apparent power is higher than the alarm value.
S. L
, Active alarm when the total apparent power is lower than the alarm value.
PF. H
, Active alarm when the power factor is higher than the alarm value.
PF. L
, Active alarm when the power factor is lower than the alarm value.
F. H
, Active alarm when the frequency is higher than the alarm value.
F. L
, Active alarm when the frequency is lower than the alarm value.
UtH.H
, Active alarm when the THD voltage is higher than the alarm value.
UtH.L
, Active alarm when the THD voltage
is lower than the alarm value.
itH.H
, Active alarm when the THD current
is higher than the alarm value.
itH.L
, Active alarm when the THD current
is lower than the alarm value.
di-1
,
Active alarm when digital input 1 is connected.
di-0
,
Active alarm when digital input 1 is disconnected.
d2-1
,
Active alarm when digital input 2 is connected.
d2-0
,
Active alarm when digital input 2 is disconnected.
With a long keystroke, press
to validate the option.
Use the keys
and
to browse through the menu screens.