6�2�1�- MODBUS ADDRESS
This screen is used to configure the device's modbus address.
Con1
Addr
0001
>3s
Con1
Addr
0001
-
-
With a long keystroke (>3s), press
to access the value's configuration.
Use the key
to modify the value of the flashing digit.
When the desired value is shown on the screen, press the
and
keys to skip the digit.
Minimum configuration value:
1
Maximum configuration value:
247
With a long keystroke, press
to validate the data.
Use the keys
and
to browse through the menu screens.
6�2�2�- BAUD RATE
In this screen, the baud rate of the RS-485 communications is selected.
bAUd
9600
>3s
bAUd
9600
Con1
-
Con1
-
With a long keystroke (>3s), press
to access the value's configuration.
Use the keys
and
to browse through the different options:
1200
, 1200 bps.
2400
, 2400 bps.
4800
, 4800 bps.
9600
, 9600 bps.
19,20
, 19200 bps.
With a long keystroke, press
to validate the option.
Use the keys
and
to browse through the menu screens.