8�- TECHNICAL FEATURES
Power supply
CirCAMP-4DP
CirCAMP-2IP
Mode
Self-powered (CH2-N)
Self-powered (L2)
Rated Voltage
230 V ~ ± 20%
127 ... 230 V ~ ± 20%
Frequency
50...60Hz
50...60Hz
Consumption
< 25 VA
< 25 VA
Voltage Measurement
CirCAMP-4DP
Connection
4 single-phase elements with shared neutral
Reference voltage
230 V
~
Frequency
(according to version)
A
B
C
50 Hz
60 Hz
50/60 Hz
CirCAMP-2IP
Connection
1 measure of three-phase voltage
Reference voltage
(according to version)
U
Q
N
3x127/220... 3x230/400 V~
3x230/400 V~
3x127/220 V~
Frequency
(according to version)
A
B
C
50 Hz
60 Hz
50/60 Hz
Current measurement
CirCAMP-4DP
Current (In)
5 A
Maximum current (Imax)
32 A
Start-up current
≤
25 mA
Self-consumption of the current circuit
0.56 VA @ 5 A
CirCAMP-2IP
Connection
2 independent measurements with current transformers
Current (In)
.../ 5 A
Maximum current (Imax)
10 A
Start-up current
≤
2 mA
Self-consumption of the current circuit
0.1 VA @ 1 A
Accuracy
Active Energy
Class B (IEC 62053-21)
Impulse inputs
CirCAMP-4DP
CirCAMP-2IP
Quantity
4
2
Type
Self-powered at +5V (Vmax = 5.1 V, Imax = 8.5 mA)
Operating
Calculating other supplies: water, gas, etc.
Maximum impedance
800 Ω
Pulse width
Ton
≥
30 ms, Toff
≥
30 ms
Installation category
CAT III 300 V
63
Instruction Manual
CirCAMP-4DP, CirCAMP-2IP
Содержание CirCAMP-2IP
Страница 1: ...INSTRUCTION MANUAL M097B01 03 16A Multifunction multimeter CirCAMP 4DP CirCAMP 2IP ...
Страница 2: ...2 CirCAMP 4DP CirCAMP 2IP Instruction Manual ...
Страница 68: ...11 CE CERTIFICATE 68 CirCAMP 4DP CirCAMP 2IP Instruction Manual ...
Страница 69: ...69 Instruction Manual CirCAMP 4DP CirCAMP 2IP ...
Страница 70: ...70 CirCAMP 4DP CirCAMP 2IP Instruction Manual ...
Страница 71: ...71 Instruction Manual CirCAMP 4DP CirCAMP 2IP ...