18
Wallbox eNext Series Installation Manual
L
N
P
E
Protections
THREE-PHASE Charge Point
•
Connect to the
400VAC
.
•
If the Power Supply is Single-
Phase, connect L1 and N.
L1
L2
L3
N
P
E
Protections
SINGLE-PHASE Charge Point
•
Connect to the
230VAC
.
Do not forget to connect the ground cable to the ground
terminal block
Make sure all screws are securely tightened at 1,5 Nm
Terminal block maximum cross-section: 10mm
2
S
Type of cable allowed by the terminal block: Copper
Cu
The three possible schemes are shown below:
1. W I R I N G D I AG R A M W I T H I N T E R N A L E L E C T R I C P R OT E C T I O N S :
In case that the installation needs protections upstream,
we highly recommend the option 2A in order to have
feedback in case of welded contact or DC leakage.