Appendix 1. Using FROM
∙FROMP/TO∙TOP Instructions
(1) S1 (base and slot number)
CIMON PLC can be expanded up to 16 bases. Following is a sample drawing of 16
bases expansion.
[Figure 10] Example of PLC-CM1 Series module extension
The first operand of FROM / FROMP instruction must be base and slot numbers. The
upper Byte is assigned as base number and the lower Byte is assigned as slot
number, so can be easily understood with hexa-decimal notation. Keep in mind that
base and slot numbers are ‘0’ based, and both the number of local base and the first
slot are zero.
Base Number
Slot
S1
Local base
Slot No. 5
H0005 or 5
1
st
expansion
Slot No. 3
H0103
10
th
expansion
Slot No. 7
H0A07
14
th
expansion
Slot No. 12
H0D0C
16
th
expansion
Slot No. 10
H100A
[Table 9] Example of setting slot number of extension function
Besides of the CIMON PLC-CM1 series, PLC-S series’ slot numbers are numbered
from one and upward.