Total Solution for Industrial Automation
7
PWM Output Module User’s manual
2
Specification
2.1
General specification
[Table 1] General specification of PWM module
Items
Specification
Standards
Operating
Temperature
-10 ~ 55 ℃ (14 ~ 131℉)
Preserving
Temperature
-25 ~ 80 ℃ (-13 ~ 176℉)
Operating
Humidity
Relative Humidity 5 ~ 95%, Avoid condensation
Preserving
Humidity
Relative Humidity 5 ~ 95%, Avoid condensation
Inner Vibration
Frequency (Hz)
Continual Vibration
Intermittent Vibration
Number
IEC61131-2
Acceleration
(㎨)
Amplitude
(mm)
Acceleration
(㎨)
Amplitude
(mm)
10 ≤ f < 57
57 ≤ f ≤150Hz
4.9 {0.5G}
0.035
9.8 {1G}
0.075
10 times
for each
direction
X, Y, Z
Inner Impact
Maximum impact acceleration : 147 ㎨ (15G)
Impression time : 11ms
Pulse wave : a sine half-wave pulse (3 times for each direction ±X, ±Y, ±Z, total on 3
times)
IEC61131-2
Inner Noise
Square wave impulse
noise
±2kV(10 minutes)
CIMON Internal
Test Standard
Electromagnetism
discharge
Voltage : 4kV(Contact Discharge)
IEC61131-2
IEC61000-4-2
Radiation EMF Noise
27 ~ 500 MHz 10V/m
IEC61131-2
IEC61000-4-3
FAST transient burst
Noise
Power supply Module
2kV
IEC61131-2
IEC61000-4-4
Digital input output (≥24V)
1kV
Digital input output (<24V)
0.25kV
Analog input output
Communication interface
Ambient
Conditions
Avoid Corrosive gas and dusts
Operating
Altitude
≤2000m
IEC61131-2
Pollution level
≤2
IEC61131-2
Colling System
Air natural cooled