EN - 15
Acce
ss
level
No. Description
Setting
Default
Display
conditions
Fan management
(continued)
2
185
Circuit 1 stage differential
2 to 6 bar
3.5
if P21 = 1, 2
3.8 if P21 = 3
If P2 = 2
2
186
Circuit 1 interstage differential
0.5 to 3 bar
0.5
If P2 = 2
2
187
Circuit 2 stage differential
2 to 6 bar
3.5
If P2 = 2
2
188
Circuit 2 interstage differential
0.5 to 3 bar
0.5
If P2 = 2
2
189
Circuit 3 stage differential
2 to 6 bar
3.5
If P2 = 2 and P3 = 3
2
190
Circuit 3 interstage differential
0.5 to 3 bar
0.5
If P2 = 2 and P3 = 3
High pressure control
3
193
Shifting of HP setpoint during total recovery
2 to 11 bar (resolution: 0.5)
4.5
If P29 = Yes
3
196
Normal condensing control return
Δ
P
0.1 to 1 bar (resolution: 0.1)
0.5
Visible if P2 = 2
2
197
Value at 0 V
10 to 25°C if P26 = 3-way valve
25°C
Visible if P2 = Water-to-water and
P26
≠
not used
2
198
Value at 10 V
25 to 40°C if P26 = 3-way valve
35°C
Visible if P2 = Water-to-water and
P26
≠
not used
Limits
3
220
Outdoor temperature, unit winter protection
2 to +6°C (resolution 1)
2
If P24 = Yes or P142 = Yes
3
221
Hydraulic module heater cut-in temperature
(ambient)
–
10 to 20°C (resolution: 1)
+
2
If P24 = Yes
3
222
Outdoor temp. differential, unit winter
protection
1 to 10 K (resolution: 1)
2
If P24 = Yes or P142 = Yes
3
225
Min. outdoor air temper. in HEATING mode
–
25 to 5°C (resolution: 1)
DISABLED
If P2 = Water-to-water and P119
≠
Cooling only
3
225.1 Max. outdoor air temp. in COOLING mode
35 to +6°C (resolution 1)
DISABLED
If P2 = Water-to-water and Air-to-
water and P119
≠
Heating only
3
225.2 Max. outdoor air temp. in HEATING mode
–
5 to 25°C (resolution: 1)
DISABLED
If P2 = Water-to-water and P119
≠
Cooling only
3
225.3 Mini. outdoor air temp. in COOLING mode
–
20 to 25°C (resolution: 1)
DISABLED
If P2 = Water-to-water and Air-to-
water and P119
≠
Heating only
2
227
Compressor 1 operation authorisation
No - Yes
Yes
2
228
Compressor 2 operation authorisation
No - Yes
Yes
2
229
Compressor 3 operation authorisation
No - Yes
Yes
If P3 = 3
Operation
1
250 LED
test
1
251 Control
setpoint
If P141
5 and
6
1
252 Outdoor
air
temperature
1
253
Evaporator water inlet temperature
1
254.1 Evaporator water outlet temperature (M1)
1
254.2 Evaporator water outlet temperature (M2)
If P3 = 3
1
257
Condenser hot water inlet temperature
If P2 = 1
1
258
Condenser hot water outlet temperature
If P2 = 1
1
261.1 Manifold water outlet temperature
If P3 = 3
1
261.2 Master/slave water outlet temperature
If P3 = 3 P28 = Yes
on master
machine
1
265
Hydraulic module temperature
If P24 = Yes
1
270 Controller
action
time
1
272
Oil warm-up time
Cut lasting between 0 and 12 hours
Cut lasting between 12 and 24 hours
If cut longer than 24 hours
0
1 h
2 h
1
273.1 Supply voltage (Module 1)
P15 = Yes
1
273.2 Supply voltage (Module 2)
If P3 = 3 and P15 = Yes
1
274.1 Machine current input
1
274.2 Current input (module 1)
If P3 = 3 and P15 = Yes
1
274.3 Current input (module 2)
If P3 = 3 and P15 = Yes
1
275.1 Machine power input
P15 = Yes
1
275.2 Power input (module 1)
If P3 = 3 and P15 = Yes
1
275.3 Power input (module 2)
If P3 = 3 and P15 = Yes
1
276.1 Electricity consumption
P15 = Yes