EN - 14
Acce
ss
level
No. Description
Setting
Default
Display
conditions
Management of setpoints
(continued)
1
122
Cooling setpoint 2
P52 + 1 K at 30°C (resolution: 0.1)
7
If P119
2, P120 = 2 or 3
1
123
Heating setpoint 1
20 to +6°C (resolution 0.1)
40
P119
1 and P120
4
1
124
Heating setpoint 2
20 to +6°C (resolution 0.1)
35
P119
1, P120 = 2 or 3
1
125.1 Low setpoint (4-20 mA) during COOLING:
P52 + 3 K at 30°C
P52 + 3
Displayed if P120 = 3 and cooling
mode activated
1
125.2 Low setpoint (4-20 mA) during HEATING
10 to 60°C
20
Displayed if P120 = 3 and heating
mode activated
1
126.1 High setpoint (4-20 mA) in COOLING mode:
P125.1
+
or
–
5 K at 30°C with minimum value of
P52 + 3
20
Displayed if P120 = 3 and cooling
mode activated
1
126.2 High setpoint (4-20 mA) in HEATING mode:
P125.2
+
or
–
5 K at 60°C with minimum value of
10°C
40
Displayed if P120 = 3 and heating
mode activated
1
127
Cooling setpoint adjustment = f (Tout)
No - Yes
No
P119
Heating
1
128 Drift
start
–
20 to 55
°
C (resolution: 1)
25
If P127 = Yes
1
129
Drift end
P128 + 5K to 60
°
C (resolution: 1)
35
If P127 = Yes
1
130
Maximum setpoint at end of drift
P52 + 3K to 30
°
C (resolution: 0.1)
15
If P127 = Yes
1
131
Heating setpoint adjustment = f (Tout)
No - Yes
No
P119
Cooling
1
132 Drift
start
–
20 to 55
°
C (resolution: 1)
15
If P131 = Yes
1
133 Drift
end
–
25 to P132
–
5K (resolution: 1)
5
If P131 = Yes
1
134
Maximum setpoint at end of drift
The highest setpoint if P120
1 or
Setpoint if P120 = 1 to 60
°
C (resolution: 0.1)
P123
If P131 = Yes
Control
2
141 Control
mode
1-Return
2-Water supply
1
If P119
2 and if P120
1 and
P120
4
2
142
Water loop winter protection
No - Yes
No
2
143
Compressor stage differential
0.5 to 5 K (resolution: 0.5)
1
If P141 = 1
2
144
Interstage differential
0.5 to 5 K (resolution: 0.5)
2
If P141 = 1
Supply with compensation by return
2
145
P coefficient
0.3 to 2 (resolution: 0.1)
1
If P141 = 2
2
146
I coefficient
0 to 1 (resolution: 0.1)
0
If P141 = 2
2
147
D coefficient
0 to 1 (resolution: 0.1)
0
If P141 = 2
2
148
T coefficient
1 to 240 seconds (resolution: 1)
15
If P141 = 2
2
149
Additional exhaust coefficient
0 to 60 seconds (resolution 1)
5
2
150
Compensation factor
0.1 to 1 (resolution: 0.1)
0.5
2
151
Compensation time
5 to P148 - 2 (resolution: 1)
8
For storage control (
Cristopia)
3
154 Storage
Yes/No
No
If P119
2 and P120
1 and P120
4
3
155
Control
Δ
T
0.5 to 10°C (resolution: 0.5)
5
If P154 = Yes
Load limit defrosting
2
170
Time between circuits (at start-up)
0 to 60 min. (10 s steps)
5 if P141
1
0 if P141=1
2
175
Load shedding via on/off input
Automatic/Selective
Auto
Fan management
2
181
HP control setpoint
7 to 13 bar (resolution: 0.5) if P1 = R134a
7 bar
If P21 = 1
8 bar
if P21 = 3
6.8
if P21 = 3
Visible if P2 = Air-to-water
2
182
Outdoor air temperature, forced HP
10 to +6°C (resolution 1)
25
if P21 = 0 or 1.
30
if P21 = 2.
Visible if P2 = Air-to-water and P29 =
No