8.6 Location
It is important for the chillers to be installed with the necessary clearances:
-
So that air discharged by the condenser is not drawn in through the intake;
-
So that maintenance can be carried out on the chiller.
If the unit is likely to be subjected to winds of above 170 km/h, it must be fixed to the ground via the Ø21 mm holes on the
base frame (mounts and bolts not supplied by CIAT).
Required clearance zone:
- 2 units: A = 2.5 m
- 3 or more units: A = 3.5 m
Maximum height of obstacles outside the
clearance zone: H = 1.6 m
1,5 m
2,5 m
A
H < 1,6 m
2,5 m
1,5 m