7.  DELIVERY - HANDLING

7.1 Delivery

The condition of the equipment must be inspected as soon as it 
is received. Check that it has not been damaged in transit and 
that there are no accessories missing. Indicate any damaged or 
missing items on the delivery slip and notify the carrier of said 
damaged or missing items by registered letter within three days 
of delivery, with a copy sent to CIAT. 

7.2 Lorry shipment:

 

During shipment, the load must be securely strapped in 
place to prevent any movement and to protect the unit from 
damage.

 

The 

LX - LXC

 

2500

 

to

 

6400

 models must be shipped 

on  a lorry whose tarpaulin can be completely removed to 
allow slings to be attached to the unit.

7.3 Container shipment:

 

The container must be of the HIGH CUBE type.

 

The red skids under the base frame can be used to slide 
the unit along the floor of the container. They must be 
removed before the unit is installed.

 

Straps can be fed through the 2 openings under the end 
cabinet in the base frame to allow the unit to be removed 
from the container:
1.  Feed the strap through the opening, around the folded 

panel and out through the bottom of the base frame.

2.  Remove the unit from the container by pulling the 2 straps.
3.  Cover the openings using the blanking covers (in order 

to prevent the unit from being lifted on a forklift truck).

1

2

3

7.4 Lifting instructions

 

These machines must be unloaded and positioned 
by a specialist handling company using the appropriate, 
standardised tools. Before handling, check that the path 
leading to the installation location is accessible and free from 
obstacles.

 

The weight and centre of gravity are shown on the handling 
label (affixed to the unit) and on the dimensional drawing.

 

Safety when lifting can only be guaranteed if all the 
instructions below are followed. Otherwise, there is a 

risk of damage to the equipment and personal injury. 

 

-

Take the time to read all of the labels affixed to the unit 
and follow the instructions they contain.

 

-

Only attach the slings to the anchorage points intended 
for this purpose and designated by labels.

 

-

Use slings with a suitable lifting capacity and follow the 
lifting instructions on the labels and drawings provided 
with the unit.

 

-

The centre of gravity is not in the middle of the unit, and 
the forces applied to the slings are therefore not always 
identical.

 

-

When lifting and positioning the unit, be careful not to tilt 
it (max. angle: 15°).

 

-

To prevent damage to the casing, use textile slings with 
shackles.

 

-

The slings must be kept apart using a spreader beam (or 
separator) to prevent damage to the casing.

 

-

Always protect the unit casing (panels, posts, roof) 
from damage during handling. Only the base frame is 
designed to withstand handling.

 

-

The unit must not be moved using a forklift 

truck.

7.5 Anchoring points for handling

Ø 50 mm

Ø 50 mm: holes for handling 
(not to be used for other purposes)

30

60

30

120

130

90

R

ecommended shackle type:

 STAS forged steel screw loop shackle

 

-

STAS code: 130M

 

-

Maximum working load: 4000 kg

Содержание POWERCIAT2 LX

Страница 1: ...POWERCIAT2 LX LXC AQUACIAT 2 Instruction manual 04 2014 N 13 47 B...

Страница 2: ......

Страница 3: ...n 15 8 3 Water quality 15 8 4 Sound level 15 8 5 Frost protection 15 8 6 Location 17 8 7 Anti vibration mounts for STD models optional 18 8 8 Anti vibration mounts for HEE models optional 22 9 CONNECT...

Страница 4: ...EAN DIRECTIVES Machinery 2006 42 EC EMC 2004 108 EC Low voltage 2006 95 EC PED 97 23 EC Category 3 2500 to 3900 HEE models 2800 to 4800 STD models and category 4 4200 to 4800 HEE models 5600 and 6400...

Страница 5: ...igned to operate with clean non corrosive fluids such as pure water soft water monoethylene glycol or monopropylene glycol Fluids such as brackish water seawater and demineralised water require a spec...

Страница 6: ...rnal sensor B18 Hydraulic module indoor environment sensor A EVAPORATOR B TANK option C SINGLE PUMP D DOUBLE PUMP POWERCIAT2 LXC Based on the POWERCIAT2 LX LXC models incorporate a complete hydraulic...

Страница 7: ...cabinet E Evaporator F Expansion vessel G Pump H Buffer tank LX C 5600X STD 6400X STD 4200X HEE 4500X HEE 4800X HEE A C D G C H E B F LX C 4200X STD 4800X STD 3200X HEE 3400X HEE 3600X HEE 3900X HEE A...

Страница 8: ...tent litres 240 283 443 560 Hydraulic connection Flexible COLLAR DN 200 Flexible COLLAR DN 250 Max pressure water end bar 10 m3 h 71 241 77 241 83 241 90 241 96 241 111 241 124 241 136 383 145 383 Air...

Страница 9: ...content litres 240 283 443 560 Hydraulic connection LX Flexible COLLAR DN 200 Flexible COLLAR 250 LXC Flexible COLLAR DN200 Max pressure water end bar 10 m3 h 63 241 70 241 77 241 83 241 89 241 95 24...

Страница 10: ...ng heating element capacity W 500 820 Maximum rated current A 1 3 2 1 Pump module heating element capacity W 1500 Maximum rated current A 3 8 LXC FROST PROTECTION BUFFER TANK OPTION 1 Evaporator pipin...

Страница 11: ...acity W 2 x 1500 Maximum rated current A 2 x 3 8 DESUPERHEATER FROST PROTECTION OPTION 1 Heat exchanger heating element power W 240 2 x 120 Maximum rated current A 0 6 2 x 0 3 REMOTE CONTROL AUXILIARY...

Страница 12: ...5 15 10 8 0 6 45 48 40 Outdoor temperature C DB Evaporator water outlet C Glycol obligatory STANDARD STD version Low Noise Version STD LN Xtra Low Noise Version STD XLN A B C 15 20 10 0 10 30 8 5 15...

Страница 13: ...eration with pure water B Full load operation must be with glycol C Operation without economiser Low Noise Version HEE LN Xtra Low Noise Version HEE XLN Partial load operation for outdoor temperature...

Страница 14: ...ion minimum volume litres 2150 2351 2551 2727 2913 3312 3696 3987 4299 POWERCIAT 2 HEE 2500X 2800X 3050X 3200X 3400X 3600X 3900X 4200X 4500X 4800X installation minimum volume litres 1967 2172 2415 249...

Страница 15: ...d and positioned by a specialist handling company using the appropriate standardised tools Before handling check that the path leading to the installation location is accessible and free from obstacle...

Страница 16: ...X 5600X 9334 6203 1002 894 1631 2167 1083 2167 1083 2167 LX 6400X 9508 6269 993 896 1631 2167 1083 2167 1083 2167 LXC 2500X 6341 3962 1052 929 545 2167 2167 2174 LXC 2800X 6378 6939 3948 4358 1052 107...

Страница 17: ...tipollution standards in force if connecting to a drinking water system 8 4 Sound level Our units are designed to operate at moderate sound levels for this type of equipment However when designing the...

Страница 18: ...3 1 7 14 Propylene glycol Freezing point C 0 4 9 16 25 Minimum water outlet C 5 4 1 4 9 Important The values are given for guidance only according to the standard characteristics of the MEG These may...

Страница 19: ...So that maintenance can be carried out on the chiller If the unit is likely to be subjected to winds of above 170 km h it must be fixed to the ground via the 21 mm holes on the base frame mounts and b...

Страница 20: ...of failure to use the recommended mounts Location of mounts for sizes 2800X 3000X STD 2151 2251 50 50 700 236 700 6506 LX 2800X 3000X 700 380 700 700 700 380 380 380 380 2251 700 A 700 7598 LXC 2800X...

Страница 21: ...00X 3600X SYLOMER 700 x 50 x 25 LXC A 3200 3400 3600 100 150 110 B 150 150 150 C 150 150 150 D 200 150 200 E 200 200 250 F 273 273 300 G 350 350 323 H 400 400 350 I 400 400 400 J 400 400 400 LXC A 320...

Страница 22: ...4200 4800 200 200 650 700 650 700 600 650 442 442 350 350 250 200 250 200 200 150 150 150 J LXC A B C D E F G H I 700 384 326 700 700 700 700 700 540 700 700 700 640 520 410 300 680 640 A 700 700 700...

Страница 23: ...D E F G H I 5600 6400 259 259 1200 1150 1100 1100 1000 1100 900 950 800 800 600 550 500 450 400 400 250 250 J LXC A B C D E F G H I 5600 6400 228 228 650 650 650 650 650 650 550 650 550 600 450 400 40...

Страница 24: ...he unit the structure or the building in the event of failure to use the recommended mounts Location of mounts for sizes 2500X HEE LXC 2151 2251 50 50 700 258 700 6506 LX 2500X 700 350 700 700 700 380...

Страница 25: ...800X 3050X SYLOMER 700 x 50 x 25 LXC A 2800 3050 400 100 B 500 500 C 500 500 D 500 500 E 200 500 F 120 120 G 113 113 H 110 110 I 110 110 J 110 110 LXC A 2800 3050 650 240 220 500 700 700 750 700 700 7...

Страница 26: ...0 x 50 x 25 SYLOMER 700 x 50 x 25 2151 50 50 2151 50 50 2251 11940 LXC 3200X 3400X 3600X 3900X SYLOMER 700 x 50 x 25 700 400 506 700 700 700 700 700 400 700 700 700 550 450 350 250 650 700 164 700 700...

Страница 27: ...YLOMER 700 x 50 x 25 2151 50 50 2151 50 50 2251 14112 LXC 4200X 4500X 4800X SYLOMER 700 x 50 x 25 700 650 550 400 550 400 450 350 350 400 700 700 700 700 700 700 700 700 700 600 700 650 650 650 650 65...

Страница 28: ...the necessary systems for filling and draining the energy transfer fluid The piping must not transmit any force or vibrations to the evaporator The pump s must be slaved to the unit auxiliary operati...

Страница 29: ...Hydraulic connections configuration and precautions To ensure that the unit is commissioned and operates under the right conditions the desuperheater water loop must be as short as possible This will...

Страница 30: ...etc and vice versa For more information refer to the Master Slave management section in the Xtraconnect 2 control manual 10 CONTROL 9 5 Electrical connections All wiring must be connected in accordanc...

Страница 31: ...circuit concerned shuts down and the fault is indicated by a message and the illumination of a red LED on the console Overpressure protection Each refrigeration circuit in each unit is equipped with a...

Страница 32: ...le 3 Re enter the setpoints 4 Start the unit by pressing the On Off button The internal safety devices are activated If one of these safety devices is triggered trace the fault reset the safety device...

Страница 33: ...e must be added to each circuit in the unit Repeat these steps if the subcooling temperature is below the specified values NB an excessively low suction pressure or an excessively high condensation pr...

Страница 34: ...of the system The lubricating oil and the low temperature liquid refrigerant in particular may cause inflammation similar to burns if they come into contact with skin or eyes Store unused refrigerant...

Страница 35: ...under or around the unit and listen for any unusual noises LP compressor suction pressure HP compressor discharge pressure the water inlet and outlet temperatures in the exchangers the charge via the...

Страница 36: ...ipate future trips Perform the checks listed in the table below if you notice that a magnitude deviates from its normal value and gradually moves closer to the safety limit Faults Probable cause Solut...

Страница 37: ...in force Check whether any part of the unit can be recycled for another purpose 14 3 Fluids to be recovered for treatment R134a refrigerant Energy transfer fluid depending on the installation water gl...

Страница 38: ...ature C Air inlet temperature C Air outlet temperature C Evaporator Water inlet temperature C Water outlet temperature C Liquid inlet temperature C Evaporator outlet temperature C Date Time Nominal vo...

Страница 39: ...EN EN 37 NA13 47 B...

Страница 40: ...NA13 47 B EN 38...

Страница 41: ......

Страница 42: ...roc der sans pr avis toutes modifications techniques Non contractual document With the thought of material improvement always in mind CIAT reserves the right without notice to proceed with any technic...

Отзывы: