3.9 - Installation of multiple chillers
It is recommended to install multiple chillers in a single row,
arranged as shown in the example below, to avoid recycling of
warm air from one unit to another.
1.5 m
min.
1.5 m
min.
If the situation at the site does not permit this arrangement, contact
your distributor to evaluate the various possible arrangements.
In certain situations an accessory (supplied loose at the time of
purchase) can be added.
3.10 - Distance from the wall
To ensure correct operation for most cases:
If h < H (2.3 m), minimum S = 3 m
If h > H or S < 3 m, contact your CIAT distributor to evaluate the
various possible arrangements. In certain situations an accessory
(supplied loose at the time of purchase) can be added.
H
S
h
Anti-vibration mounts
3 - DIMENSIONS, CLEARANCES