POWERCIAT LX ST/HE/XE
EN-
20
4.2 - Electrical data
LX ST/HE units 3428 to 4608
LX ST/HE
3428
3828
4008
4408
4608
Power circuit supply
Nominal voltage
V-ph-Hz
400-3-50
Voltage range
V
360-440
Control circuit supply
24 V via internal transformer
Maximum operating input power
(1)
- LX ST/HE
Standard unit
kW
Circuit 1
(a)
kW
198
226
269
288
311
Circuit 2
(a)
kW
288
314
287
309
311
Single power connection point option
kW
485
539
556
596
622
Unit with Xtra & Super Low Noise option
Circuit 1
(a)
kW
190
218
258
276
298
Circuit 2
(a)
kW
277
301
276
297
298
Single power connection point option
kW
466
519
533
573
597
Power factor at maximum power
(1)
- LX ST/HE
Standard unit
Displacement Power Factor (Cos Phi)
0,88
0,88
0,88
0,88
0,88
Unit + Xtra & Super low noise option
Displacement Power Factor (Cos Phi)
0,88
0,88
0,88
0,88
0,88
Nominal unit current draw
(2)
- LX ST/HE
Standard unit
Circuit 1
(a)
A
255
271
345
358
394
Circuit 2
(a)
A
354
394
358
390
394
Single power connection point option
A
609
665
703
748
789
Unit + Xtra & Super low noise option
Circuit 1(a)
A
242
258
326
339
373
Circuit 2(a)
A
337
373
339
371
373
Single power connection point option
A
579
631
665
710
747
Maximum operating current draw (Un)
(1)
- LX ST/HE
Standard unit
Circuit 1
(a)
A
322
368
443
473
512
Circuit 2
(a)
A
469
512
473
508
512
Single power connection point option
A
791
880
916
981
1025
Unit with Xtra & Super Low Noise option
Circuit 1
(a)
A
309
355
424
454
491
Circuit 2
(a)
A
452
491
454
489
491
Single power connection point option
A
761
846
878
943
983
Maximum current (Un-10 %)
(1)
- LX ST/HE
Standard unit
Circuit 1
(a)
A
322
368
443
473
512
Circuit 2
(a)
A
469
512
473
508
512
Single power connection point option
A
791
880
916
981
1025
Unit with Xtra & Super Low Noise option
Circuit 1
(a)
A
309
355
424
454
491
Circuit 2
(a)
A
452
491
454
489
491
Single power connection point option
A
761
846
878
943
983
Start-up current
(3)
- LX ST/HE
Standard unit
Circuit 1
(a)
A
587
587
629
629
629
Circuit 2
(a)
A
629
629
629
629
629
Single power connection point option
A
Single power connection point option & Opt 25c
A
687
702
729
744
744
Unit + Xtra & Super low noise option
Circuit 1
(a)
A
587
587
629
629
629
Circuit 2
(a)
A
629
629
629
629
629
Single power connection point option
A
687
702
729
744
744
Single power connection point option & Opt 25c
A
Maximum start-up current (Un)
(2)
- LX ST/HE
Standard unit
Circuit 1
(a)
A
587
587
629
629
629
Circuit 2
(a)
A
629
629
629
629
629
Single power connection point option
A
687
702
729
744
744
Unit + Xtra & Super low noise option
Circuit 1
(a)
A
576
576
613
613
611
Circuit 2
(a)
A
615
611
613
613
611
Single power connection point option
687
702
729
744
744
(1) Values at the unit's permanent maximum operating condition (as shown on the unit's nameplate).
(2) Values at the unit's maximum operating condition (as shown on the unit's nameplate).
(3) Maximum operating current of the smallest compressor(s) + fan c locked rotor current of the largest compressor.
(4) Standardised EUROVENT conditions, water-cooled exchanger inlet/outlet = 12°C/7°C, outdoor air temperature = 35°C.
(a) When the machines are equipped with two power supplies, circuit 1 is intended to supply refrigerant circuit A and circuit 2 supplies the refrigerant circuit B.
For units LX3428 to 4608: circuit 1 supplies circuit A, circuit 2 supplies circuit B.
4 - PHYSICAL PROPERTIES AND ELECTRICAL DATA FOR LX UNITS