6 - OPERATING PRINCIPLE
Activation of the electric heater power stages
Stage 3
Stage 2
Stage 1
1/3 WINTER gradient
Setting 13
2/3 WINTER gradient Setting 13
3/3 WINTER gradient - Setting 13
WINTER setpoint temp. - Setting 02
The electric heater stages are activated 30 seconds after the fan motor assembly is turned on
7 - USER SETTINGS
N°
Description
Possible choices
00
Operating mode:
Used to set the control box's
operating mode
Unit
-
WintEr
(used for heating)
SuMMEr
(ventilation only)
Min
-
Max
-
Defaut
WintEr
Increment
-
01
Override:
Allows the user to override the
control mode being used
Unit
-
Off
CFt
(Confort)
ECO
(Economy)
H.GL
(Frost Protection)
tIMe
(depending on time schedule)
Min
-
Max
-
Defaut
CFt
Increment
-
02
Temperature setpoint in
WINTER
mode
Unit
°C
From 0 to 51°C
Min
0
Max
Setting 03 - 0.2°C
Defaut
18
Increment
0.2
03
Temperature setpoint in
SUMMER
mode:
Ventilation only
Unit
°C
Min
Setting 03 + 0.2°C
Max
51
From 0 to 51°C (Ventilation only)
Defaut
18
Increment
0.2