12.5 Operating Mode
12.6 Interruption Time
The Interruption Time, controlled by the selector switch located on the Receiver electronic
module, can have a value between
40 and 500 ms
. This adjustment allows the optimisation of
the detection
Sensitivity
to suit a particular installation condition.
Increase the Interruption Time, decrease the sensitivity
.
12.7 Power Control
The Power Control, adjusted by the appropriate switch located on the Transmitter electronic
module, can have a value between 40 and 100 (100 mt Optical) or 60 and 160 (160 mt Optical).
This setting is based on the length of the zone of the installed barrier. See the following list:
Model
Setting the power based on the zone
IR Optical
Module 100
Value
40
60
80
100
Zone length
0-40m
40-60m
60-80m
80-100m
IR Optical
Module 160
Value
60
100
130
160
Zone length
0-60m
60-100m 100-130m 130-160m
“
AND
” Mode :
“
OR
” Mode :
Simultaneous
interruption of the two
optical modules for
intrusion alarm
Interruption of one of
the two optical modules
for an intrusion alarm.