F086 Instant Power-Off Restart Function Setting Range:0~2 Factory Setting: 0
F086=0: Ineffective
F086=1: Continuous Operation after power comes back.
F086=2: Restart when power comes back.
Function Instruction: Such function is used to set the motor's operation way when instant
power-off and power back.
Note 1: When choosing ineffective (F086=0), when instant power-off and power back,
the motor will not start and will alarm for under voltage.
Note 2: When choosing Continuous Operation after power comes back (F086=1), when
instant power-off and power back, the motor will operate according to the power
-off state, it is applicant to high inertance load.
Note 3: When choosing Restart when power comes back (F086=2), when instant power
-off and power back, the motor will restart according to the power-off state, it is
applicant to normal load.
Note 4: When the Inverter is set the function of Instant Power-Off Restart Function,
please set Danger sign or else in conspicuous place in front of the machine
device, in order not to cause accident for the machine will suddenly start when
the power comes back.
F087 Frequency Reach Setting Setting Range: 0.0~400.0HZ Factory Setting: 0.0HZ
Function Ins truction: Such function is used to set the reach signal point of the operation
frequency, through output signal by multi-function output port (Y1,Y2). Y1,Y2 multi-
function output terminal have one of which to choose frequency reach setting
(details in function code F098, F099 function choice), otherwise this function will be
ineffective. When frequency reach to the setting, there will be output of DC 24V
50mA between multi-function terminal and COM terminal.
F088 Analogue Input Gain Setting Range: 0~200% Factory Setting: 100%
Function Instruction: when frequency input is analogue signal input, ratio of the maxim
um output freque ncy value with relevant frequency set signal value is frequency gain
( in another word, when input signal is not more than 10V/20mA, throug h adjusting
analogue input gain, it can also reach 10V or 20mA frequency). It can also be used
to the compensation of the frequency setting.
Frequency
Top Frequency
50% Top Frequency
Frequency set signal
F089 Analogy Output Choice Setting Range: 0~2 Factory Setting: 0
F089=0: Analogy Frequency Count.
F089=1: Analogy Current Count.
F089=2: Analogy Voltage Count.
Function Instruction: Such function is used to remote monitoring of the Inverter output
frequency, output voltage, or output current, through connecting a DC analogue
pointer type frequency count, voltage count or current count between AFM+ and
COM terminals.
F090 Analogy Output Gain Setting Range: 50~150% Factory Setting: 100%
Function Instruction: Such function is used to adjust (F089) the error of analogy signal
output value and actual value.
F091 Start Display Choice Setting Range: 0~8 Factory Setting: 0
F091=0: Display output frequency.
F091=1: Display output current.
F091=2: Display output voltage.
F091=3: Display DC bus bar voltage.
F091=4: Display motor rotation speed.
F091=5: Display PID target value.
F091=6: Display PID feedback value.
F091=7: Display counter value.
F091=8: Display module temperature.
Function Instruction: Such function is used to set the display content when Inverter
starts.
F092 Speed Coefficient Setting Range: 0.00~99.99 Factory Setting: 30.00
Function Instruction: Such function is used to the ratio of the speed display value with
actual frequency, then make the speed display speed coincident with the actual
motor rotation speed.
Speed display value = output frequency X speed display coefficient
For example: Output frequency: 50.0HZ motor's speed is 1500 round/minute.
Then set value = motor speed 1500 / output frequency 50 = 30.