F086   Instant Power-Off Restart Function    Setting Range:0~2    Factory Setting: 0

F086=0: Ineffective

F086=1: Continuous Operation after power comes back.

F086=2: Restart when power comes back.

Function Instruction: Such function is used to set the motor's operation way when instant 
             power-off and power back.

Note 1: When choosing ineffective (F086=0), when instant power-off and power back, 
             the motor will not start and will alarm for under voltage.
Note 2: When choosing Continuous Operation after power comes back (F086=1), when 
             instant power-off and power back, the motor will operate according to the power
             -off state, it is applicant to high inertance load.
Note 3: When choosing Restart when power comes back (F086=2), when instant power
             -off and power back, the motor will restart according to the power-off state, it is 
             applicant to normal load.
Note 4: When the Inverter is set the function of Instant Power-Off Restart Function, 
             please set  Danger  sign or else in conspicuous place in front of the machine 
             device, in order not to cause accident for the machine will suddenly start when 
             the power comes back.

F087   Frequency Reach Setting    Setting Range: 0.0~400.0HZ  Factory Setting: 0.0HZ

Function Ins truction: Such function is used to set the reach signal point of the operation 
     frequency, through output signal by multi-function output port (Y1,Y2). Y1,Y2 multi-
     function output terminal have one of which to choose  frequency reach setting  
     (details in function code F098, F099 function choice), otherwise this function will be 
     ineffective. When frequency reach to the setting, there will be output of DC 24V 
     50mA between multi-function terminal and COM terminal.

F088   Analogue Input Gain      Setting Range: 0~200%     Factory Setting: 100%

Function Instruction: when frequency input is analogue signal input, ratio of the maxim
     um output freque ncy value with relevant frequency set signal value is frequency gain 
     ( in another word, when input signal is not more than 10V/20mA, throug h adjusting 
     analogue input gain, it can also reach 10V or 20mA frequency). It can also be used 
     to the compensation of the frequency setting.

Frequency 

           Top Frequency

50% Top Frequency

Frequency set signal

F089       Analogy Output Choice    Setting Range: 0~2      Factory Setting: 0

F089=0: Analogy Frequency Count.

F089=1: Analogy Current Count.

F089=2: Analogy Voltage Count.

Function Instruction: Such function is used to remote monitoring of the Inverter output 
      frequency, output voltage, or output current, through connecting a DC analogue 
      pointer type frequency count, voltage count or current count between AFM+ and 
      COM terminals.

F090     Analogy Output Gain      Setting Range: 50~150%    Factory Setting: 100%

Function Instruction: Such function is used to adjust (F089) the error of analogy signal 
     output value and actual value.

F091     Start Display Choice      Setting Range: 0~8         Factory Setting: 0

F091=0: Display output frequency.

F091=1: Display output current.

F091=2: Display output voltage.

F091=3: Display DC bus bar voltage.

F091=4: Display motor rotation speed.

F091=5: Display PID target value.

F091=6: Display PID feedback value.

F091=7: Display counter value.

F091=8: Display module temperature.

Function Instruction: Such function is used to set the display content when Inverter
      starts.

F092     Speed Coefficient     Setting Range: 0.00~99.99    Factory Setting: 30.00

Function Instruction: Such function is used to the ratio of the speed display value with 
      actual frequency, then make the speed display speed coincident with the actual 
      motor rotation speed.
Speed display value = output frequency X speed display coefficient

For example:  Output frequency: 50.0HZ motor's speed is 1500 round/minute.
          Then set value = motor speed 1500 / output frequency 50 = 30.

Article6    Function parameter illustration

Article6    Function parameter illustration

Содержание ZVFG7 series

Страница 1: ...ZVFG7 SERIES ZVFP7 SERIES INVERTER USER S MANUAL INVERTER...

Страница 2: ...ble shooting and etc of inverters Ensure that this manual is made available to the final user and keep it handy for future reference If there is any doubt or question please contact the Technical Serv...

Страница 3: ...4 3 The content of dispay 27 Article 5 Run in test 28 5 1 Run in test 29 5 2 Operation of run 30 Article 6 Reference on Function Data 31 6 1The fleet of function data 32 6 2Detail reference of functi...

Страница 4: ...ment failure Do not touch any active componentsin the inverter for high voltage remains in it when the indicator light isON after the power cut Cautions for Installation and connection The installatio...

Страница 5: ...rrotate Do not modify the set parametervalue for inverter if there isno special requirement for the factory default settinghas been done properly Otherwise it may cause damage to the inverter or equip...

Страница 6: ...ease open the carton and check it as soon as you got the products Checking item 1 check the Inverter destroied or not 2 Packing box concluding a piece of Inverter a brochure 3 Check the name plate be...

Страница 7: ...ing output 250V 2A contact open electric pole output Other function Diagram run PID restart after transient stop restart after accident frequency down up data locking crawl function absorbing function...

Страница 8: ...he sunshine without dust without combustible and corrosion gas No granule of metal or foam ofmetal place No shake no electro magnetic interference place 3 1 2 Caution of installation The board must be...

Страница 9: ...U V W otherwise it will destroy the Inverter Dangerous It is forbidden to connect the wire when the Inverter is in use Be sure to operate it when cut off the power after five minutes The terminal blo...

Страница 10: ...S T connectfreely Output terminal U V W connect the three phrase motor if you find the rotating reverse please adjust the two phrase arbitrary The Inverte r below 15KW concluding the brake unit if yo...

Страница 11: ...terminal Positive rotata stop Reverse stop Accident exterior Accident reset Multi speed 1 Multi speed 2 Multi speed 3 Crowl function Positive rotate after connecting COM break stop Reverse rotate afte...

Страница 12: ...00A 400A 1 5 2 5 2 5 4 6 6 10 10 16 16 25 25 35 35 50 50 70 3 2 4Directory of complement electric Complement of circuit breaker magnetic starter and the width of wire with the Inverter Article 3 Insta...

Страница 13: ...nel 1 Control panel 2 with potentIometer RLN STOP JOG FWD REV JOG PRGM REV FUNG DATA RUN STOP RESET JOG PRGM REV FUNG DATA RUN STOP RESET FWD REV JOG STOP LED display area Display current status run s...

Страница 14: ...an choose the position of modify data Illustration of indicator Title of indicator Illustration Stop Positive Reverse Crawl After the Inverter connect the power and it is not start the indicator is li...

Страница 15: ...tion Illustration Display F000 enter into the function setting Press four times display F004 Press one time 0 in the between is flashing Press one time display F014 Press one time the forward 0 is fla...

Страница 16: ...he output voltage of the run Display the AC voltage of bus bar wire Display the present speed of the Inverter Display the feedback data when PID run Display the data setted when PID run Display the da...

Страница 17: ...play reduce from P50 0 to P0 0 if everything is ok operate the next step Inverter stop to output motor stop rotate run in test finish Gernerally please repeat servral times from the first step to the...

Страница 18: ...teriorTerminal control positive start stop reverse stop 2 ExteriorTerminal control positive start stop reverse positive 3 ExteriorTerminal control positive start reverse start stop Choice of frequency...

Страница 19: ...ency F004 0 1 999 9S 0 1 999 9S Highest frequency F004 0 1 999 9S 0 1 999 9S Highest frequency F004 5 0Hz 10 0S 10 0S 10 0Hz 10 0S 10 0S 20 0Hz 10 0S 10 0S 30 0HZ 10 0S 10 0S 40 0HZ Multi speed run Fu...

Страница 20: ...rting AC brake torque 0 0 25 0S 0 0 25 0HZ 0 30 0 3 s 3 0HZ 4 Counter funtion Function code Title function Range of setting Factory parameter Note Counter mode Counter parameter 0 Expiry 1 Mode of up...

Страница 21: ...nction choice 0 Multi speed 1 1 Multi speed 2 2 Multi speed 3 3 Exterior lift button 4 Exterior fall button 5 Exterior crawl function 6 Normal close botton 7 Exterior stop free 8 counter 9 counetr to...

Страница 22: ...nal F002 Frequency Setting Way Choice Setting Range 0 4 FactorySetting 0 F002 0 Frequency is set by key on panel F002 1 Frequency is set by potentiometer on panel F002 2 Frequency is set by outer pote...

Страница 23: ...ncy Factory Setting 25 0HZ Function Instruction Such function isused to set therandom middle frequencyvalue of V F curve Note Middle frequency top value is limited by the highest frequency F004 bottom...

Страница 24: ...owlimit F015 Note 2 Frequency lowlimit top value is limited by frequency toplimit F014 Top Frequency Frequency Toplimit Frequency Lowlimit Top Frequency Frequency input sigal F016 Start Frequency Sett...

Страница 25: ...eleration Time Crawl Instruction Time Crawl Deceleration Time Multi Speed Operation In multi speed operation F000 is the operation frequency of the first sector F018 is the acceleration time ofthe fir...

Страница 26: ...or 7 speed when the Inverter is operated in multi speed or by program Function Instruction These functions are used to set the frequency acceleration time deceleration time of the sector 8 speed when...

Страница 27: ...aximum Target Value Setting Range 0 9999 Factory Setting 1000 Function Instruction Such function is used to set the maximumtarget value when PID is operated F068 Relevant Feedback Value of Maximum Tar...

Страница 28: ...everse Carrier Wave Frequency abridged general view is as below Carrier Wave Frequency Electromagnetism Noise Disturbance Leakage Current Fever Value Large Small Small Large Small Large Note Carrier w...

Страница 29: ...ut is analogue signal input ratio of the maxim um output freque ncy value with relevant frequency set signal value is frequency gain in another word when input signal is not more than 10V 20mA throug...

Страница 30: ...put frequency and continue recovery to operation frequency after voltage restored to be normal F102 Acceleration Over current Stall prevention Function Setting Setting Range 80 180 Factory Setting 130...

Страница 31: ...ruction After fault Inverter will restore operation totally 10 times are allowed to restore operation after fault of every power on F112 Fault Restart Wait Time Setting Range 0 60S Factory Setting 10S...

Страница 32: ...connected terminal phases Load change suddenly Accelerate time too short Motor jammed turn Inverter inner malfunction Input voltage abnormal Decelerate time to short Unsuitable braking component Load...

Страница 33: ...Yes No Yes No Yes No 7 2 2 Over voltage over voltage when accelerating when decelerate when constant speed over voltage over voltage OU 1 Decrease the power voltage to be within the bound of regulate...

Страница 34: ...stic Change to use out connected thermal relay Whether the over current setting is suitable Rectify the setting value Whether the on load is too big Maybe because of mal function or mal operating Plea...

Страница 35: ...unction Yes No No Yes Yes Yes No No Yes No Yes Yes No No Yes Yes No No Yes Yes No No Yes Yes No No No Yes No Yes No Yes Yes No No Yes 7 3 2 Motor could operate but couldn t change speed Motor could op...

Страница 36: ...hip on the circuit board Attention please don t leave tool and other eyewinker inthe Inverter or else it ll bring malfunction Attention please close the cover and screwedtightly after the examination...

Страница 37: ...it board Other device 2 3 years 4 5years 5 8years According to the examination conditions Transportation and Deposit 8 2 1 transportation of Inverter put the Inverter upward when transport it acutely...

Страница 38: ...0T 4150T 300 180 280 130 168 7 d A B W Outline dimension and installation dimension Article9 Outline dimension and installation dimension Article9 Outline dimension and installation dimension Type Pow...

Страница 39: ...g to this using handbook or problem induced by repair and rebuildpersonally without permission Problem induced by using beyond the standard requirement Damage induced by move or storage afterpurchasin...

Страница 40: ...rating panel out press downward the arrow directs emphatically by hand then pull out the operating panel 2 Install the leading out panel on the Inverter 3 Put the pulled out operating pane l in the in...

Страница 41: ...the Inverter then the Inverter could be repaired and maintained conveniently Please don t use it as the daily on and off switch for the Inverter Magnetic contactor It s unnecessary to install magneti...

Отзывы: