9
Alarm output
1. Specifications
Item
Specification
Alarm area
1 area
Alarm set value
2 values in a specified area
Setting resolution
1 degree (°C/ºF)
Alarm activation condition
When consecutive 4 frames have satisfied the alarm
condition
Alarm reset condition
When the measured temperature returns from the
alarm set value in 4 images continuously
Output Control
Auto Alarm Reset/Manual Alarm Reset
Resetting condition of alarm
output manual reset
Rebooting of the thermal image sensor
Command from a PC
Alarm Output
Non-voltage contact output
Number of outputs
2 points [Alarm name: AL1 (alarm 1), AL2 (alarm 2)]
Output logic
Output logic selectable (N.O/N.C)
Alarm condition
Selectable (high-limit, low-limit)
Alarm condition when power is off Opened
2. Image storage
The image data can be stored when alarm is activated.
Item
Content
Number of storage
1 image
An image can be stored by AL1 or AL2 (to be
specified).
Storage medium
Built-in EEPROM
Storage data
Temperature data (without time stamp)
Storage timing
Every time when the alarm is activated/when the first
alarm is activated only
Selectable by a PC (Refer to Page 10.)
Reading of stored data
Can be retrieved from a PC
Erasing of stored data
Automatic erasing or erasing by a command with the
alarm setting from a PC