5.5.3 Programming modulation time constant
The modulation time constant is programmed on the signal modulation modes.
The first-order lag
degree can be adjusted by the modulation time constant.
The increase of modulation time constant
makes the first-order lag degree increase and the temperature measured is displayed smoothly.
・
Press MODE key to get the modulation time constant programming screen.
・
Press
key to shift the digit and press
key to program the modulation time constant.
・
For programming to Hold, increase the value by
key at the most significant digit to
display “Hold”.
・
Press [ENT] key to store the time constant programmed.
The programming range of the modulation time constant is 0.0 to 99.9 seconds (0.1 second step) and
“Hold”
.
・
The default time constant is 0.0 second.
・
Operation when the modulation time constant is programmed to “Hold”.
By programming the signal modulation mode to Peak, the maximum
temperature in measurement is held.
By programming the signal modulation mode to Valley, the minimum
temperature in measurement is held.
By programming the signal modulation mode to Delay, the temperature
measured is displayed on condition that the modulation time constant is
99.9 seconds