[DB600] General Instruction Manual
MODE 2
- 76 -
□
□□
▲
SEL
↑
↓▼
SEL
Step time
Sets a step time necessary.
"
□□
"
to
"
"
Time necessary of step
Use the [
], [
] and [ENT] keys to set the step time.
Use the [>] key to move the cursor to the right digit.
"Program operation time unit (MODE2)" needs to be set before setting the step time.
The time unit can be set at "Program operation time unit (MODE2)".
□□
▲
SEL
↑
↓▼
SEL
Execution No. selection
for program operation
Specify the parameter to be used in a step by execution No. The following
parameters can be selected by setting an execution No.
Event 1, Event 2, Event 3, Event 4
PID
Output limiter L, Output limiter H
Guaranty soak
"
□□
"
Same execution parameter No. as the last step No.
"
□□
"
to
"
□□
"
Execution parameter No. 1
to
Execution parameter No. 8
Use the [
], [
] and [ENT] keys to set the execution No. selection for program
operation.
When 0 is set, the execution No. used in the last step No. will be inherited. This is
effective on the step 0 immediately after pattern link or pattern repeat.
□
▲
SEL
↑
↓▼
SEL
E
n
d
s
te
p
s
e
tti
n
g
Pattern No./
end step No.
Displays or selects an arbitrary pattern No./step No.
"
□
"
to
"
□
"
Displays the setting screen of step No. 00 of pattern No. 1
displayed when the [SEL] key is pressed.
Displays the setting screen of step No. 13 of pattern No. 4
displayed when the [SEL] key is pressed.
Use the [
] or [
] key to select an arbitrary pattern No./step No. screen.
Pressing the [
] key displays the pattern No./middle step No. or pattern No./start
step No. screen.
Pressing the [
] key displays the pattern No./start step No. or pattern setting screen.
No parameter is set by the [ENT] key.
Step No. is displayed up to the number of steps + 1.
□
□
▲
SEL
↑
↓▼
SEL
Output 1 at END
Sets the output 1 in the program operation END status.
"
□
"
Constant value control performed with the displayed SV
"
□□
"
to
"
□
"
Fixed value output [%]
Use the [
], [
] and [ENT] keys to set the output 1 at END.
Use the [>] key to move the cursor to the right digit.
This does not function in a pattern to which a pattern link is set.
For the case the pattern repeat has been set, this function works after the repeat
operation finishes.
The order of priority for output parameters are shown below.
Preset manual output by external signal input
↑ (High)
Priority
↓ (Low)
MANUAL output
RESET output (0%)
PV abnormal output
END output
AUTO output