[DB600] General Instruction Manual
MODE 2
- 73 -
□□□
▲
SEL
↑
↓▼
SEL
Program/
constant value
operation switch
Switches the operation between program operation and constant value operation.
"
□□
"
Operation screen switches to the constant value operation
screen to perform constant value operation.
"
□□□
"
Operation screen switches to the program operation screen to
perform program operation.
Use the [
] or [
] and [ENT] keys to make a switch between the program and
constant value operations.
[Actions taken when a switch to constant value operation is made]
When a switch to constant value operation is made in the program operation RESET
status, "RUN/READY switch (operation screen)" is set to READY.
When a switch to constant value operation is made in the status other than program
operation RESET, "RUN/READY switch (operation screen)" is set to RUN. Also,
"Constant value operation PV start (MODE1)" becomes effective.
"Execution No. selection for program operation (MODE2)" changes to "Execution
No. selection for constant value operation (operation screen)".
The program operation status changes to the RESET status.
[Actions taken when a switch to program operation is made]
When a switch to program operation is made while "RUN/READY switch (operation
screen)" is set to READY, the program operation RESET status is entered.
When a switch to program operation is made while "RUN/READY switch (operation
screen)" is set to RUN, the program operation RUN status is entered.
□
□□
□
▲
SEL
↑
↓▼
SEL
Program operation
time unit
Selects a unit for each step time necessary.
"
□□ □
"
[Hour : Minute] is used for step time.
"
□□ □
"
[Minute : Second] is used for step time.
Use the [
] or [
] and [ENT] keys to set the program operation time unit.
When the time unit is set/changed during program operation (RUN/STOP/END), the
program operation RESET status is entered.
Check each step time after setting the step time unit. The unit of "Step time
(MODE2)" will not be changed automatically even when the program operation time
unit is changed.
□□□
▲
SEL
↑
↓▼
SEL
SV in RESET
Sets SV in the program operation RESET status.
"
"
to
"
"
SV in program operation RESET
* The setting range is limited by "SV limiter (MODE5)".
Use the [
] or [
] and [ENT] keys to set the SV in RESET.
Use the [>] key to move the cursor to the right digit.
SV in RESET will not affect the control calculation.
When "SV transmission" is selected for "Transmission type (MODEa and MODEb)"
of digital/analog remote, the transmission value during program operation RESET
can be set/changed.