[DB600] General instruction manual
- 129 -
Function
Description
"
"
Event reset
Resets (clears) the event output.
Controls the specified external signal input with instantaneous signal. Resets the event
output after approx. 0.5 seconds or more from entering the conduction (ON) state. The
non-conduction (OFF) state is entered immediately after a reset to restore the normal
condition. If the conduction (ON) state is kept, the reset state will continue.
"
□
"
"
□
"
"
□
"
"
□
"
Execution No.
selection 1
Execution No.
selection 2
Execution No.
selection 4
Execution No.
selection 8
Sets the execution No. selection for constant value operation.
The execution No. selection is performed based on the control signals of BCD codes 1, 2,
4 and 8.
Operation by keys or communication will be disabled.
Controls the specified external signal input with continuous signal. See the following table
for the relation between the BCD code and execution No. Bring the external signal input
into conduction (ON) depending on the desired execution No. The execution No. is
selected after approx. 0.5 seconds or more from entering the conduction (ON) state.
Execution
No. 8
Execution
No. 7
Execution
No. 6
Execution
No. 5
Execution
No. 4
Execution
No. 3
Execution
No. 2
Execution
No. 1
SV8
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
SV4
OFF
ON
ON
ON
ON
OFF
OFF
OFF
SV2
OFF
ON
ON
OFF
OFF
ON
ON
OFF
SV1
OFF
ON
OFF
ON
OFF
ON
OFF
ON
When the BCD code other than the above (execution No. 1 to 8) is selected, the execution
No. will not be changed and the previous No. will be retained.
Operation by keys or communication is unavailable while the execution No. selection for
constant value operation is assigned to the external signal input. To select the execution
No. for constant value operation by keys on the constant value operation screen, set the
external signal input to the BCD code other than the above (execution No. 1 to 8).
Generally, bring all the four external signal inputs into non-conduction (BCD code: 0) to
select the execution No. for constant value operation on the constant value operation
screen.
As an example, it is possible to assign only the three external signal inputs: SV1, SV2 and
SV4 when only the execution No. 1 to 4 are required.
"
"
Program/constant
value
operation switch
Switches the operation between program and constant value operation.
Controls the specified external signal input with continuous signal. Switches to the program
operation RUN status after approx. 0.5 seconds or more from entering the conduction (ON)
state, or switches to the constant value operation RUN status after approx. 0.5 seconds or
more from entering the non-conduction (OFF) state.
The execution condition and operation are the same as those described in the section
4-3-3 "Program operation method".
"
□
"
Program operation
RUN/STOP
Switches the operation status between RUN and STOP in program operation.
Controls the specified external signal input with continuous signal. Switches to the RUN
status after approx. 0.5 seconds or more from entering the conduction (ON) state, or
switches to the STOP status after approx. 0.5 seconds or more from entering the
non-conduction (OFF) state.
The execution condition and operation are the same as those described in the section
4-3-3 "Program operation method".
"
□
"
Program operation
ADVANCE
Advances the program pattern step.
Controls the specified external signal input with instantaneous signal. Advances the step
by one when the non-conduction (OFF) state is entered after approx. 0.5 seconds or more
in the conduction (ON) state.
The execution condition and operation are the same as those described in the section