- 8 -
(1) Insert the unit into the panel cutout from the front of the panel.
(2) Fix the unit to the panel using the brackets (tightening torque: 1.0Nm). Brackets are attached to the top and
bottom surfaces.
2. Mounting condition
To avoid accidents, make sure to read and understand the following.
Industrial environment
Select a location distant from sources of electric field or magnetic field and without mechanical vibration or shock.
● Overvoltage category ...... II (EN standard)
● Altitude ........................... 2000m or less
● Pollution degree .............. 2 (EN standard)
● Working place ................ Indoor
Normal operating condition
● Ambient temperature ··· 0 to 50
℃
(20 to 65%RH,non-condensing)
● Ambient humidity ········· 20 to 80%RH,non-condensing(5 to 45
℃
)
● Power voltage ············· General specification : 100 to 240V AC
±
10%
● Power frequency ········· General specification : 50/60Hz
±
2%
Atmosphere
● For safety, avoid a location with corrosive gas, explosive gas, flammable gas and combustible gas.
● Avoid a location with dust, smoke, or steam.
Mounting angle
● Lateral tilting ················ 0 to 10°
● Longitudinal tilting ······· Forward tilting: 0°Backward tilting: 0 to 30°
● View angle ··················· -10 to +30°with the horizon as the standard
Angles other than the above affect the recording operation.
!
Caution
Slide
Indicator
View angle
About 30°
About 10°
Panel thickness
(2 to 6mm)
Brackets