R410A50Hz Universal Outdoor Series Technical Manual Duct Type Indoor Unit
57
GD Chigo Heating & Ventilation Equipment Co., Ltd.
6.10 CTH-48HR1
MODEL
CTH-48HR1
COOLING
OUTDOOR TEMPERATURE DRY
Indoor Conditions
21ºC
25ºC
30ºC
35ºC
40ºC
45ºC
21ºC DB
15ºC WB
Total capacity kW
13.52
12.94
12.47
11.76
11.29
10.94
Sensitive capacity kW
10.82
10.35
9.97
9.41
9.03
8.75
Input kW.
2.96
3.38
3.81
4.23
4.65
5.08
24ºC DB
17ºC WB
Total capacity kW
14.81
14.17
13.65
12.88
12.36
11.98
Sensitive capacity kW
11.85
11.33
10.92
10.30
9.89
9.58
Input kW.
3.13
3.57
4.02
4.47
4.91
5.36
27ºC DB
19ºC WB
Total capacity kW
16.10
15.40
14.84
14.00
13.44
13.02
Sensitive capacity kW
12.88
12.32
11.87
11.20
10.75
10.42
Input kW.
3.29
3.76
4.23
4.70
5.17
5.64
32ºC DB
23ºC WB
Total capacity kW
18.52
17.71
17.07
16.10
15.46
14.97
Sensitive capacity kW
14.81
14.17
13.65
12.88
12.36
11.98
Input kW.
3.78
4.32
4.86
5.41
5.95
6.49
6.11 CTH-60HR1
MODEL
CTH-60HR1
COOLING
OUTDOOR TEMPERATURE DRY
Indoor Conditions
21ºC
25ºC
30ºC
35ºC
40ºC
45ºC
21ºC DB
15ºC WB
Total capacity kW
15.47
14.73
14.28
12.21
12.91
12.5
Sensitive capacity kW
12.37
11.83
11.4
10.75
10.32
10.02
Input kW.
3.73
4.34
4.84
5.36
5.92
6.44
24ºC DB
17ºC WB
Total capacity kW
16.93
16.17
15.53
14.70
13.11
13.75
Sensitive capacity kW
13.74
12.91
12.43
11.74
11.34
10.67
Input kW.
3.65
4.34
5.11
5.64
6.24
6.81
27ºC DB
19ºC WB
Total capacity kW
17.25
16.6
16.2
16.2
15.34
14.83
Sensitive capacity kW
14.72
14.11
13.54
12.7
12.3
11.81
Input kW.
4.17
4.75
5.36
5.97
6.54
7.18
32ºC DB
23ºC WB
Total capacity kW
21.14
20.22
19.5
18.36
17.67
17.12
Sensitive capacity kW
16.92
16.17
15.61
14.71
14.13
13.7
Input kW.
4.91
5.43
6.17
6.90
7.55
8.23