Chapter 4. Controls
Loop
Output threshold
N
active
If set, this flag indicates that the threshold
N
(where
N
is either 1
or 2) is active for the given output.
Proportional control enabled
If set, this flag indicates that the proportional control is active in the
current PID configuration.
Integral control enabled
If set, this flag indicates that the integral control is active in the current PID
configuration.
Derivative control enabled
If set, this flag indicates that the derivative control is active in the current
PID configuration.
Bumpless transfer enabled
This flag is set when bumpless transfer is enabled.
Integral wind-up protection enabled
This flag is set when integral wind-up protection is enabled.
Integral wind-up protection active
If set, this flag indicates that integral wind-up protection is cur-
rently active.
Boost enabled
This flag is set when the boost feature is enabled.
Boost active
If set, this flag indicates the control is currently modified by the boost feature.
Boost Inhibited
This flag is set when the boost feature is inhibited from further activation.
4.1.2.8
Error Flags
The error flags show any problems causing an error for a device. These flags can either be active or
not. To see the state of these error flags, select:
Options
→
Device Flags
→
Error Flags
Flags that are active are shown in black text on a white background, those that are not active are
grayed out. Available flags are:
Process run/stop signal error
If set, this flag indicates that the control can not read the state of the
run/stop signal.
Process variable read error
This flag is set if the control can not read the process variable.
Loop
Output alarm
N
active
If set, this flag indicates that the alarm
N
(where
N
is either 1 or 2) is
active for the given output.
Loop
is either primary, secondary or tertiary (most controls only have
a primary output).
Error reading PID setpoint
If set, this flag indicates the control is unable to read the setpoint value
when using dynamic setpoints.
Fail-safe mode active
This flag is set if the control enters failsafe mode.
Overfeed protection active
This flag is set if over feed protection has been activated.
4.1.2.9
Diagnostics
The PID controller diagnostic information can be accessed using:
Options
→
Diagnostics
Содержание HydroAct HA4
Страница 1: ...HydroAct 4 User Manual Chemtrac Inc Firmware Version 1 19 November 15 2017...
Страница 8: ......
Страница 9: ...I 2 Overview 11 2 1 Safety Precautions 2 2 Technical Data 2 3 Installation 2 4 Operation Analyzer...
Страница 10: ......
Страница 32: ......
Страница 34: ......
Страница 42: ...42 Chapter 3 Sensors For safety and correct operation the sensor must be properly earthed...
Страница 74: ......
Страница 92: ......
Страница 93: ...III 6 Warranty 95 7 Returns 97 7 1 Contact Details Documentation...
Страница 94: ......
Страница 96: ......