RIM-Protocol Converter User Guide - Version 1.0
Chatsworth Products, Inc. (CPI) • 800-834-4969
53
Table 4.2 Read Output Registers Packet Structure
Table 4.3 Output Registers
4.3
RTU Framing
The example below shows a typical Query/Response from an Protocol Converter.
Table 4.4 Response Sample
Slave address 2 responds to Function Code 4 with six bytes of hexadecimal data and ends with CRC16 checksum.
Register Values:
40001 = 0000 (hex)
40002 = 0000 (hex)
40003 = 0001 (hex)
Code
Name
Description
Units
Range
40001
Integer Output
Register for Integer data
16
0-65535
42001
Float Output
* two registers need
Register for Float data
32
0-65535
Read Registers Request Packet
Read Registers Response Packet
Slave Address (1 byte)
Slave Address (1 byte)
03 (Function code) (1 byte)
03 (Function code) (1 byte)
Start Register (2 bytes)
Byte count (1 byte)
# of registers to read (2 bytes)
First register (2 bytes)
CRC Checksum (2 bytes)
Second register (2 bytes)
…
CRC Checksum (2 bytes)
Slave
Address
Function
Code
Count Bytes
of Data
Register
Data
Msb Lsb
Register
Data
Msb Lsb
Register
Data
Msb Lsb
CRC 16
“Lsb”
CRC 16
“Msb”
02
04
06
00 00
00 00
00 01
B5
A3