RIM-Protocol Converter User Guide - Version 1.0
Chatsworth Products, Inc. (CPI) • 800-834-4969
47
Table 3.9 BACnet Server Configuration Options (continued)
Figure 3.28 BACnet PICS Information
Option
Description
UDP Port
This is the user datagram protocol port, which is used by applications to send
messages to a device (in this case, the Protocol Converter).
Enter 0 to specify port 47808 as the UDP port. If another port is specified by
your application, enter a new port number in this field.
Default setting: 0 (47808)
BACnet-MS/TP Port3 Max
Master
Set the slave address, 1/127. 0 = slave only.
Default setting: 0
BACnet/IP Read-Multiple
Enable or disable this feature.
BACnet PICS link
This link displays the protocol implementation conformance statement (PICS).
The PICS Web page shows general BACnet capabilities of the device
(for example, available LAN options). An example of a BACnet PICS page is
shown in
Figure 3.28
.
Engineering Units
Click this link to view a list of the units supported by the device, coupled with
their numerical BACnet identifiers.
BACnet/IP COV Clients
This is a list of the BACnet clients that will receive a notification when t
he Protocol Converter notes a change of value (COV).
Configure these addresses on the Registers tab.
BACnet BBMD-BDT
This feature is used by some BACnet masters for discovery on different subnets.
Enter information as applicable to your application.