MAINTENANCE ANd STORAGE
Storage
The generator should be started at least once every 14
days and allowed to run for at least 20 minutes. For
longer term storage, please follow these guidelines.
Generator Storage
1. Add a properly formulated fuel stabilizer to the tank.
2. Be sure all appliances are disconnected from the
generator.
3. Run the generator for a few minutes so the treated
fuel cycles through the fuel system and carburetor.
4. Turn the fuel valve to the “Off” position.
5. Let the generator run until fuel starvation has
stopped the engine. This usually takes a few minutes.
6. The generator needs to cool acompletely before
cleaning and storage.
7. Clean the generator according to the maintenance
section.
8. Change the oil.
9. Remove the spark plug and pour about 1⁄2 ounce
(14.8 mL) of oil into the cylinder. Crank the engine
slowly to distribute the oil and lubricate the cylinder.
10. Reattach the spark plug.
11. Store the unit in a clean, dry place out of direct
sunlight.
Battery
Some frame type generators are equipped with an
automatic battery charging circuit. The battery will
receive charging voltage when the engine is running. The
battery will maintain a proper charge if the unit is used
on a regular basis (about once every two weeks). If it is
used less frequently, the battery should be connected
to a trickle charger or battery maintainer to keep the
battery properly charged. If the battery is not able to
start the engine, it can be started by manually pulling
the engine recoil cord. If the battery voltage is extremely
low, the charging circuit may not be able to re-charge
the battery. In this case, the battery must be connected
to a standard automotive style battery charger for re-
charging before it can be used.
disconnect the Battery
1. Remove the protective cover from the black/negative
battery lead.
2. Disconnect the black/negative lead from the black/
negative terminal on the battery and store the cap
screw and lock washer.
3. Repeat steps 1-2 for the red/positive battery lead.
4. Store the battery in a cool, dry place.
A Float Charger will maintain the battery condition
over long storage periods.
NOTE
Charge the Battery
For generators equipped with batteries for electric
starting, proper battery maintenance and storage should
be followed. An automatic battery charger (not included)
with automatic trickle charging capability should be used
to charge the battery. Maximum charging rate should not
exceed 1.5 amps. Follow the instructions included with
the battery charger. The battery should be fully charged
at least once per month.
Generator exhaust contains odorless and colorless
carbon monoxide gas.
To avoid accidental or unintended ignition of your
electric start generator during periods of storage,
the following precautions should be followed:
– When storing the generator for short periods of
time make sure that the Ignition Switch and the
FuelValve are set in the OFF position.
– When storing the generator for extended periods
of time make sure that the Ignition Switch and
the Fuel Valve are set in the OFF position and
the battery leads have been disconnected from
the battery.
dANGER
TROUBLESHOOTING
Problem
Cause
Solution
Generator will not start
No fuel
Add fuel
Faulty spark plug
Replace spark plug
Unit loaded during start up
Remove load from unit
Generator will not start;
Generator starts but runs roughly
Low oil level
Fill crankcase to the proper level
Place generator on a flat, level surface
Choke in the wrong position.
Adjust choke.
Spark plug wire loose
Attach wire to spark plug
Generator will not start electrically
Generator battery is dead
Recharge generator battery
Generator shuts down during operation
Out of fuel
Fill fuel tank
Low oil level
Fill crankcase to the proper level. Place
generator on a flat, level surface
Generator cannot supply enough power or
overheating
Generator is overloaded
Review load and adjust. See “Power
Management”
Insufficient ventilation
Check for air restriction. Move to a well
ventilated area
No AC output
Cable not properly connected
Check all connections
Connected device is defective
Replace defective device
Circuit breaker is open
Reset circuit breaker
Faulty brush assembly
Replace brush assembly (Service Center)
Faulty AVR (auto voltage regulator)
Replace AVR (Service Center)
Loose wiring
Inspect and tighten wiring connections
Other
Contact the help line.
Generator gallops
Engine governor defective
Contact the help line
Repeated circuit breaker tripping
Overload
Review load and adjust. See “Power
Management”
Faulty cords or device
Check for damaged, bare or frayed wires.
Replace defective device