4.4.1 Electric wiring diagram of standard single-probe
Remote-type ultrasonic level meter:
Diagram of standard single-channel Remote-type wiring terminals
Wiring Method:
Grounding:
1) Make sure the grounding terminal of the meter is actually grounded and the me-
ter does not share ground terminal with other equipment
2) Connect terminal 4.
3) Ground resistance must be less than 4 Ω
Transducer:
red wire: connected to Trans1 (transducer);
blue wire: Temp 1 + temperature
Black wire: GND (ground wire)
Current Output:
“c” connected to mA1 +; “current -” connected to mA- /
GND
Relay:
RLlnA and RLnB are normally open;
To ensure the default state of relay is “normally open”, RLlnA and RLnB shall be con-
nected. RlnA and RLnC are normal closed.
To ensure the default state of relay is “normally closed”, RLlnA and RLnC shall be
connected.