32
11.3 Operation data Midi Wall 130
Primary side
Heating
DHW
Design pressure PS
16 Bar
6 bar
10 Bar
Design temperature TS
120°C
90°C
90°C
Relief pressure safety-valve
-
3 Bar
9 Bar
Volume Heat exchanger, L
2,987/1,957 L
3,090 L
2,06 L
CB60-60L
Temperature
program (°C)
Heating
Capacity CB
Plates Plates
Plates
Flow P dPp Flow S dPs
kW
type
no
primary
secondary
l/s
kPa
l/s
kPa
100-63/60-80
128,5
60
60
1*29 L
1*30 L
0,86
3,9 1,57
8,7
100-53/50-70 (52,75) 169,6
60
60
1*29 L
1*30 L
0,89
4,2
2,06
15,0
100-48/45-60 (46)
126,6
60
60
1*29 L
1*30 L
0,58
1,9
2,05
15,0
100-43/40-60 (42,15)
168,4
60
60
1*29 L
1*30 L
0,73
2,8
2,04
15,0
100-43/40-70
106,3
60
60
1*29 L
1*30 L
0,47
1,2
0,86
2,9
100-43/40-80
41,5
60
60
1*29 L
1*30 L
0,18
0,2
0,25
0,3
100-36/33-40 (33,06) 58,47
60
60
1*29 L
1*30 L
0,22
0,3
2,01
15,0
100-33/30-60
133
60
60
1*29 L
1*30 L
0,50
1,4
1,07
4,5
CB60-40L:2
Temperature
program (°C)
DHW
Capacity CB
Plates Plates
Plates
Flow P dPp Flow S dPs
kW
type
no
primary
secondary
l/s
kPa
l/s
kPa
80-23/10-60 (19,1)
157
60
40
1*10 1*9
2*10 L
0,62
23,0
0,75 29,9
80-23/10-60 (18,1)
134
60
40
1*10+1*9
2*10 L
0,52
16,6
0,64 22,3
80-23/10-55 (16,2)
141
60
40
1*10+1*9
2*10 L
0,53
17,5
0,75 30,2
80-23/10-55 (15,35)
121
60
40
1*10 +1*9
2*10 L
0,45
12,7
0,64 22,5
70-25/10-55 (19,8)
141
60
40
1*10 1*9
2*10 L
0,67 27,2 0,75 29,9
70-25/10-55(18,7)
121
60
40
1*10 +1*9
2*10 L
0,56
19,4
0,64
22,3
70-22/10-55 (19,75)
141
60
40
1*10+1*9
2*10 L
0,67
27,1
0,75
29,9
70-22/10-55 (18,7)
121
60
40
1*10+1*9
2*10 L
0,56
19,4
0,64
22,3
65-22/10-55
126
60
40
1*10+1*9
2*10 L
0,70 29,3 0,66 24,1
65-22/10-55 (21,7)
121
60
40
1*10+1*9
2*10 L
0,67
26,5
0,64
22,1