6.4 Heating circuit pump Grundfos Magna3 25–100, settings and capacity
The pumps have been factory-set to AUTOADAPT without automatic night setback.
AUTO
ADAPT
(factory set)
•
Recommend control mode for most heating systems.
•
Automatically adjusts the pump to actual system characteristics.
•
Ensures minimum energy consumption and a low noise level.
•
Reduced operating costs and increased comfort.
6.4.1 Heating circuit pump Grundfos Magna3 25-100, capacity
Picture 12
6.4.2 Grundfos Eye operating indications
Grundfos Eye
Indication
Cause
No lights are on.
The power is off.
The pump is not running.
Two opposite green indicator lights
running in the direction of rotation
of the pump.
The power is on.
The pump is running
Two opposite green indicator lights
are permanently on.
The power is on.
The pump is not running.
One yellow indicator light running
in the direction of rotation of the
pump.
Warning.
The pump is running.
One yellow indicator light is
permanently on.
Warning.
The pump has stopped.
Two opposite red indicator lights
flashing simultaneously.
Alarm.
The pump has stopped.
One green indicator light in the
middle is permanently on in
addition to another indication.
Remote-controlled.