Cetetherm Midi Wall TA
Installation, service and operating instruction
17
7.1.4 Nosie in the DHWC system
Reason
Action
The DHWC pump capacity set too high
Reduce the pump capacity
Reduce the pump capacity by selecting a lower setting on the pump
when needed.
Air in the DHWC pump
Vent the DHWC pump
Set the pump to speed III. Loosen the pump motor end nut to and let it
stay opened until the air in the pump is released. When the pump has
been vented, i.e. when the noise has ceased, set the pump according
to the recommendations.
The DHWC pump motor or pump
component damaged
Change pump components or the complete DHWC pump
See
9.3 Change the complete DHWC pump or pump components
7.2 Heating system, service instruction
7.2.1 Heating system temperature too high or too low
Reason
Action
The heating control equipment may
need to be adjusted
Check and adjust the heating curve
See separate instruction.
Heating circuit strainer clogged
9.2 Clean the heating circuit strainer
Heating valve and/or actuator does not
work
8.2 Check the function of the heating actuator and valve.
7.2.2 No heating
Reason
Action
Circulation pump not running
Check that the electrical power is on.
Check pre-set heating parameters in the controller.
Air pockets in the substation or in the
heating circuit
Check the circulation pump
If the pump fails to start after stopping, start the pump at the highest
setting.
Vent the pump
The pump is self-venting.
Possible remaining air in the pump may cause noise. This noise
ceases after a few minutes run time.
Heating circuit strainer clogged
9.2 Clean the heating circuit strainer