It is important for the communications parameters of the PMC-1302-3 ESG’s P2 to be programmed to
match those of the PMC-660. The IP Port Number for P2 is 20001.
Figure 5-3 P2’s Setting
After the P2 settings of the PMC-1302-3 ESG has been correctly configured, click
Reboot
on the
left-hand pane and then click the
Reboot
button on the right-hand pane to save the settings. The
PMC-1302-3 ESG will perform a reboot operation with the new configuration. When the Log-In page
returns, the PMC-1302-3 ESG is now ready.
Figure 5-4 Reboot Page
5.3 Configuring PecStar iEMS
In PecStar iEMS’s
PecConfig
interface, select
Site 1
on the left-hand pane and then click on the
Properties
icon to bring up the
Site Properties
dialog box.
Figure 5-5 Systemconfig Interface
In this example,
P1
of the PMC-1302-3 ESG is used, and
Site 1
has been configured with the following
parameters:
1.
Drive Type = MODBUS Protocol Master Site Driver
2.
Polling Mode = Serial
3.
Port Type = Ethernet
4.
IP = 192.168.0.127
5.
Port = 20001 (for P2 of PMC-1302-3 ESG)