The LEDs stop scrolling. Then, the
A Selection
LED lights solid, and the other
LEDs go out.
This indicates that the timeout is set to four minutes (standard factory
configuration).
6. To increase the timeout, flip the
Select/Next
switch (
S07
)
UP
and release it.
7. To decrease the timeout, flip the
Select/Next
switch (
S07
)
DOWN
and release it.
8. When the
RF
LED is lit solid, it indicates that a time of one minute will be added.
When the
Bat
LED is lit solid = two minutes;
A Selection
LED = four minutes;
B
Selection
LED = eight minutes.
Note: This is a binary representation. So, if the RF and A Selection LEDs are lit
solid
—and the others are unlit—you have a five-minute timeout.
9. When the
RF
LED is blinking, the timeout = 20 minutes. When the
Bat
LED is
blinking = 30 minutes;
A Selection
LED blinking = 45 minutes;
B Selection
LED
blinking = 60 minutes; and all four LEDs blinking = infinite timeout.
10. Once you have chosen your desired timeout, press and release the green
Horn/Start
pushbutton (
S09
) to return to
Maintenance Mode
.
11. Press the green
Horn/Start
pushbutton (
S09
) again to return to operational
mode.