FIRESTAR COMBUSTION CONTROLLER - VERSION 6.7 • OPERATION MANUAL

Demand Mode (High)

Status

Fan

Primary

Secondary Connected

Power

IGNITION

AIR

LED RED

LED RED

When the combustion temperature reaches 750˚F, both the primary and the 

secondary air actuators will be fully open and their status LEDs will be red.

Idle Transition Mode

Status

Fan

Primary

Secondary Connected

Power

IGNITION

AIR

As the water temperature setpoint is reached in Demand Mode, the primary 

air actuator will close to stop combustion and the Primary status LED will 

turn off. The combustion fan will stay on for a moment with the secondary air 

actuator open, and then the fan will shut off. The secondary air actuator will 

close a short time later. This transition mode allows the combustion process to 

ramp down and burn off the gasification products before the furnace goes into 

idle.

Содержание Fire Star

Страница 1: ...ER Save This Manual For Future Reference 1 AUG 2018 p n 9000645 For parts and accessories service or repairs call your authorized Central Boiler dealer or heating contractor Record the information bel...

Страница 2: ......

Страница 3: ...5 Standby Idle 5 Idle Pulse 6 Demand Mode Low 6 Demand Mode Medium 6 Demand Mode High 7 IdleTransition Mode 7 Door Open 8 Ignition Air 8 Basic Controller Features 9 AdjustingWaterTemperature Setpoint...

Страница 4: ...sage to alert you Before operating the FireStar Combustion Controller become familiar with the information the control panel provides and with the procedures for making changes to settings 1 Power but...

Страница 5: ...actuator will open helping to light the fire in the firebox Outdoor Furnace Operation Power When the controller is off the LED display will be off To turn the controller on or off press the Power butt...

Страница 6: ...Temperature Setpoint minus the Water Temperature Differential the controller will enter Demand Mode In Demand Mode the primary air actuator will slowly open to the correct setting for the furnace mod...

Страница 7: ...Status Fan Primary Secondary Connected Power IGNITION AIR As the water temperature setpoint is reached in Demand Mode the primary air actuator will close to stop combustion and the Primary status LED...

Страница 8: ...cools to less than 550 F The Secondary status LED will be illuminated while the actuator is open DOOR OPEN will be displayed in the LED display Ignition Air Status Fan Primary Secondary Connected Pow...

Страница 9: ...ton at the same time This monitor will reset to 00 00 each time the furnace is loaded with wood i e the firebox door is left open for more than 30 seconds To manually reset this monitor press the Igni...

Страница 10: ...ter temperature displays for 6 seconds and the combustion temperature in the Reaction Chamber displays for 3 seconds during normal operation To briefly display the Reaction Chamber temperature press t...

Страница 11: ...ble to the desired setting Press the Menu button to save the setting and return to Setup Mode To Exit Setup Mode Wait 10 seconds without pressing any buttons and the controller will automatically exit...

Страница 12: ...ERATURE The idle pulse will continue until the temperature in the Reaction Chamber is above this temperature To effectively disable the pulse to temperature feature lower this value to its minimum set...

Страница 13: ...te furnace operation will stop and the display will flash special characters to indicate the update process The entire process should take about 5 minutes Do not disconnect power during this process I...

Страница 14: ...en for more than 30 seconds This will allow operation for one loading must override each loading until a repair can be made Do not override this alarm if the system has a leak NOTE If water is added t...

Страница 15: ...ction Chamber temperature until it senses that the water temperature has fallen below 195 F HIGHTEMP2 The external high limit sensor has sensed that the water temperature is above 200 F and has discon...

Страница 16: ...er BYPASS The bypass door is open if applicable to your model DOOR OPEN The firebox door is open TC1 TC2 TC3 or A 1 If the display indicates any of these messages contact your dealer STEP FAIL 1 STEP...

Страница 17: ...a 1 4 nut driver or socket remove the two screws and open the control panel 3 Remove the round plug on the left side of the control 4 Install the grommet into the hole 5 Align the antenna through the...

Страница 18: ...n LED will flash blue while it is attempting to connect When the LED is a steady green the control is connected to your network 15 If the control fails to connect the connection LED will be steady red...

Отзывы: