background image

26

Section 1 - Outdoor Furnace Installation

Radiant Floor System Installations

Installing radiant floor heating is a very viable heating 

option when either remodeling or building new. Radiant 

floor heat can also be added to an existing home easily 

if  the  floor  joists  are  exposed  (as  in  an  unfinished 

basement). Piping may be installed in a wide variety of 

configurations and locations including, but not limited 

to, the following:

•  In a concrete slab
•  Within the subfloor system (e.g., Gyp-Crete®)
•  Within the floor joist system
•  Within the walls or ceilings

When installing piping between floor joists (16" or 41 

cm on center) run two 1/2" pipes between each joist. 

Insulate below the piping to prevent excessive heat in 

the lower level.
Proper insulation is key to effective radiant heating and 

controlling large heat demands. Heat from this type of 

system radiates equally in all directions. As an example, 

if piping is installed in a slab, the ground below the slab 

must be dry and well-insulated. If not properly insulated, 

nearly 50% of the heat will be wasted warming the 

ground below the slab. Two inches (5 cm) of blueboard 

insulation is recommended. Two 1" (2.5 cm) layers of 

blueboard can be used. This allows lapping of the joints 

in the 4' x 8' (122 x 244 cm) sheets.

NOTE:  Do  not  use  beadboard  (expanded 

polystyrene), bubble foil or roll-out foam insulation.
NOTE:  A  minimum  of  one  inch  (2.5  cm)  of 

insulation should be used. Two inches (5 cm) of 

insulation and vapor barrier below the insulation 

is recommended.

Areas with high water tables need to be prepared 

properly to prevent contact between the ground water 

and insulation.
For examples of radiant heating systems using 1/2" 

piping in the loops, refer to Fig. 29 through Fig. 32.
The spacing of each circuit is 12" (30.5 cm) between 

pipes. The water circulates in opposite directions to 

provide an even distribution of heat. The mixing valve 

regulates the temperature of the water circulating 

through the loops by mixing return water with the hot 

supply water. In applications where high heat loss is 

expected, loop spacing may be reduced to 10" (25 cm) 

or less. If additional information is desired, contact your 

dealer.

NOTE: The longer the loop length, the lower the 

flow  rate  and  the  lower  the  heating  capacity. 

Loop  lengths  greater  than  350  feet  (107  m)  are 

not recommended.
NOTE:  The  temperature  of  the  water  used  in 

radiant  heating  should  be  determined  by  the 

installer in accordance with the application.
NOTE:  It  is  not  uncommon  that  it  can  be  very 

difficult to get a concrete slab up to temperature  

in late fall or early winter in a new building that 

is not completely sealed and not well insulated. 

Once the building is completely sealed and well 

insulated,  bringing  the  slab  up  to  temperature 

can still take a considerable amount of time and 

wood; however, once warm, wood consumption 

will be reduced if the concrete slab and building 

are insulated properly .
NOTE:  For  zone  installations,  refer  to  Fig.  30 

(multi-zone) or Fig. 32 (single zone).

Insulation

Insulation

Poly Vapor 

Barrier

Soil/Sand

Slab

Footing

Ground Level

Plate

Slab on grade

Slab

Wire

Mesh

Insulation

Vapor Barrier

2" Blueboard Styrofoam

®

is recommended (minimum

of 1" Blueboard Styrofoam

®

).

Basement

Insulation

Insulation

Poly Vapor 

Barrier

Soil/Sand

Slab

Footing

Ground 

Level

Plate

(For Slab on Grade or Basement)

Radiant Floor Heat

Hot Supply Return

© 2013 Central Boiler

NOTE: If the temperature of the 

concrete slab is below freezing 

(32˚F), there must be adequate 

antifreeze in the system, or the 

slab must be pre-heated, before 

water is circulated through the 

radiant slab system.

 Fig. 29

Содержание e-Classic 1450 IR

Страница 1: ...personal injury or loss of life Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any a...

Страница 2: ...re determined under the same test conditions using higher heating value lower heating value and annual fuel utilization efficiency AFUE This heater meets the 2015 U S Environmental Protection Agency s...

Страница 3: ...Direct Circulation Baseboard Installation 25 Radiant Floor System Installations 26 Pool and or Hot Tub Heating 29 FILLING OUTDOOR FURNACE WITH WATER AND PURGING AIR 30 SECTION 2 OPERATING INSTRUCTION...

Страница 4: ...ce water temperature is below 100 F and or there is no charcoal base left in the firebox E Classic Refueling Tips Following a few easy tips when you re refilling your E Classic with wood will help to...

Страница 5: ...tallation Section 2 Operating Instructions Section 3 Maintenance Section 4 Owner Serviceable Items Section 5 Troubleshooting Section 6 General Information Anyone owning or operating this outdoor furna...

Страница 6: ...he electrical power to the outdoor furnace before replacing an electrical component WARNING Should overheating occur or the gas supply fail to shut off do not turn off or disconnect the electrical sup...

Страница 7: ...ir dried seasoned hardwoods as compared to softwoods or to green or freshly but hardwoods DO NOT BURN any wood that is not clean wood unseasoned wood garbage tires lawn clippings leaves brush trimming...

Страница 8: ...the hot supply and return water lines and insulation Be sure to maintain the required clearances to combustibles and recommended maintenance clearances ThermoPEX pre insulated piping is recommended f...

Страница 9: ...damaged If something is located within the fall zone and cannot be removed guy wires or braces may need to be installed to prevent a falling chimney from causing damage see Fig 2 NOTE If more than thr...

Страница 10: ...the existing heat emitter s To prevent freezing if the outdoor furnace is not fired for extended time periods or if lengthy power outages are anticipated during cold weather a nontoxic propylene glyco...

Страница 11: ...the ground rod is below the ground surface 2 Route the ground wire from the ground rod under the outdoor furnace base and over to the frame of the outdoor furnace 3 Secure the ground terminal with a...

Страница 12: ...14 2 two wires plus ground underground rated wire should supply the outdoor furnace with electricity A heavier gauge wire may be needed if the run is over 200 feet 61 meters Check local codes and requ...

Страница 13: ...nnection must be tested for leaks before placing the appliance in operation HIGH ALTITUDE INSTALLATIONS High altitude derating instructions are included with the Gas fired Wood Ignition Burner Kit CIR...

Страница 14: ...r furnace is 10A 120VAC and 60Hz A The pump motor must be installed in a horizontal position B The junction box must not be located below the pump motor see Fig 10 If necessary remove the four screws...

Страница 15: ...bove the pump should be adequate for systems with higher resistance e g longer loops with other fittings elbows heat exchangers For systems with low resistance e g short loops larger diameter pipes an...

Страница 16: ...valve A thermostatic valve must be installed on each set of supply and return lines in the system to maintain the outdoor furnace water temperature above 150 F 65 C Operating the outdoor furnace with...

Страница 17: ...15 Section 1 Outdoor Furnace Installation...

Страница 18: ...r thermostatic mixing valve is to be installed in the hot water outlet from the water heater Install a tee in a fitting on the top of the water heater see Fig 18 for the hot water heat exchanger NOTE...

Страница 19: ...heat exchanger it should be mounted in the center without gaps on the sides that would allow air to flow around the heat exchanger All air must be directed through the face of the exchanger Air flow d...

Страница 20: ...85 F 85 C minimum NOTE On multi speed fans cap and tape off any extra wires NOTE Installer must comply with all applicable codes and regulations NOTE This configuration allows use of a 24 volt thermos...

Страница 21: ...ine between the outdoor furnace and thermostatic valve Outdoor furnace water temperature setpoint should be set at 185 F minimum NOTE Forced Air System and Water Heater Heat Exchanger Components p n 1...

Страница 22: ...operate if the outdoor furnace is out of fuel Refer to Fig 22 for one possible arrangement 2 An alternative method is to install a line voltage thermostat to control the blower on the forced air furn...

Страница 23: ...need for manifolds for mounting of up to two pumps on the outdoor furnace NOTE Pump s may be installed on the outdoor furnace or inside the building NOTE If a Taco 014 pump is used the pump should be...

Страница 24: ...be water baseboard heaters or panel radiators 2 A water to air heat exchanger with a thermostatic ally controlled fan can be installed in the lower part of the building being heated Fig 24 This can in...

Страница 25: ...ely 165 F 74 C of water temperature transfer The temperature controller on the outdoor furnace may be adjusted to allow the outdoor furnace to reach water temperatures up to 195 F 91 C Each system wil...

Страница 26: ...urge the air from the indoor system by closing the valves on the outdoor furnace then pressurize the indoor system with water from the domestic water line CAUTION Do not apply more pressure to the ind...

Страница 27: ...ig 27 and 28 illustrate direct circulation baseboard installation examples This horizontal assembly must not exceed a height of 4 inches 10 cm above top of water heater NOTE Outdoor furnace water temp...

Страница 28: ...Fig 29 through Fig 32 The spacing of each circuit is 12 30 5 cm between pipes The water circulates in opposite directions to provide an even distribution of heat The mixing valve regulates the temper...

Страница 29: ...27 Section 1 Outdoor Furnace Installation Fig 30 Fig 31...

Страница 30: ...28 Section 1 Outdoor Furnace Installation Fig 32 Fig 33...

Страница 31: ...may cause severe personal injury death or substantial property damage CAUTION Do not operate the outdoor furnace frequently or for extended periods of time with the water temperature below 150 F 65 C...

Страница 32: ...eel 1 Connect the male end of garden hose A to valve 1 using the backflow preventer and two 3 4 female hose x 3 4 male pipe adapters p n 4928 Connect the female end of the garden hose to valve 2 2 Clo...

Страница 33: ...t 17 Refer to Firing the Outdoor Furnace to fire up the outdoor furnace CAUTION Be sure the outdoor furnace is filled with water before firing Never fire the outdoor furnace when the water level is mo...

Страница 34: ...the firebox and increased wood consumption Increased moisture in the firebox can result in corrosion Unseasoned wood causes reduced performance lower combustion rates and lower heat output The full he...

Страница 35: ...lection and Preparation in the Introduction In order for wood to burn the moisture in the wood must first be evaporated boiled off The more moisture there is in the wood the more energy it will consum...

Страница 36: ...become familiar with your particular conditions This will allow you to identify cause and effect in a variety of circumstances and what works best for your conditions CAUTION Do not burn plastic garba...

Страница 37: ...pull the bypass door handle toward the front of the outdoor furnace and push down to close the bypass door 8 After the water temperature is above 150 F 66 C proceed to Adding Heat Load Cold Start Fir...

Страница 38: ...operation Leaving the bypass door open during operation may cause damage to components of the outdoor furnace and may cause creosote buildup that can prevent the bypass door from sealing properly NOT...

Страница 39: ...ble as the firebox door is opened because smoke and hot gases escaping through the firebox door opening could ignite From a safe distance observe the fuel load WARNING Use extreme care when adding woo...

Страница 40: ...e firebox door is open uncontrolled amounts of air entering the firebox can accelerate combustion It is very important to leave the bypass door open for 15 seconds after closing and latching the fireb...

Страница 41: ...the firebox and air channels will not dry NO DRYING Very little radiant heat to dry air channels High humidity Reloading at this level can restrict airflow and create excessive coals or too deep of a...

Страница 42: ...ly until interval for your application can be determined D When new after three months then every six months thereafter F Frequency will vary depending on heat load requirements type of wood used and...

Страница 43: ...ow burning fire As a result cresote residue accumulates on the flue lining When ignited this creosote makes an extremely hot fire The chimney connector and chimney should be inspected at least twice m...

Страница 44: ...e of ash 3 Remove any heavy or solidified ash CAUTION Always wear the appropriate personal protective gear when cleaning ash from the firebox and the Reaction Chamber 4 Disposal of ashes Ashes should...

Страница 45: ...g out Leaking air caused by an improperly fitting cover can cause corrosion Fig 49 3 7 Heat Exchangers 1 Press the Power button on the FireStar controller to turn it off CAUTION Be sure to turn off th...

Страница 46: ...t be tipped back as shown before lifting it out Thermocouple Fig 53 5 Install the refactory end cap by tipping it forward before setting it in place Close the Reaction Chamber door and install the win...

Страница 47: ...d without testing that power is disconnected 2 Open the rear access door then inspect the combustion air fan inlet screen and fan wheel and clean if necessary Make sure the air intake is clean and not...

Страница 48: ...tighten the hose clamp 8 Connect the power leads to the solenoid 9 Close the airbox cover then close the rear access door 10 Connect the electrical power to the outdoor furnace at the main power sour...

Страница 49: ...shown in Fig 61 Use a hoe to pull the ash to the rear of the furnace then use a small shovel to remove all of the ash and deposits from the Reaction Chamber Take care not to damage or move the firebri...

Страница 50: ...chamber then insert the heat exchanger scraper and drop it down the chamber while holding on to the second chain Once the heat exchanger scraper drops to the bottom of the heat exchanger drop the seco...

Страница 51: ...el that is too high the results should be verified using a new test kit The pH test strips and Permanganate Reagent each have a varying shelf life that can affect their accuracy Test kits should be st...

Страница 52: ...05 If antifreeze has been added to the water use Test Kit p n 597 3 Dip the pH test strip from the test kit in the water sample Shake excess water off the test strip Compare the color of the test stri...

Страница 53: ...m the furnace remove the plug from the unused supply port to prevent damage from water freezing in the supply port pipe Fig 64 Flushing the System If the system water is brown or orange it is an indic...

Страница 54: ...etely fill them When the start of the seal is reached cut the end of the seal about an inch longer than required at an angle that matches the starting end then remove the seal from the groove Fig 66 3...

Страница 55: ...ere with the new seal 4 Apply a liberal amount of silicone sealant into the entire Reaction Chamber door seal groove 5 Starting at the center of the hinge side of the Reaction Chamber door insert the...

Страница 56: ...that power is disconnected Make sure the power cannot be reconnected while servicing the solenoids i e use lock out tag out 2 Open the airbox cover located at the rear of the outdoor furnace NOTE Smo...

Страница 57: ...the alignment hole in the refractory modules THERMOCOUPLE 1 Disconnect power to the outdoor furnace WARNING Do not proceed without testing that power is disconnected Make sure the power cannot be rec...

Страница 58: ...will help to dry out the wood loaded on top of those pieces Is the coal bed the correct depth One to three inches 2 5 to 7 5 cm of glowing coals are needed to optimize the operation of the outdoor fur...

Страница 59: ...he outdoor furnace with a very hot bed of coals or a raging fire in the firebox If after closing the firebox door the bypass door is closed too quickly the fire can actually be put out Gases will cont...

Страница 60: ...essure in the chimney may be incorrect and adding more chimney sections may be required However due to many variables even if exhaust does not come out from around the cover the chimney might still no...

Страница 61: ...plies power to the outdoor furnace check that it is on 3 Circuit breaker on airbox off Check that the circuit breaker switch on the airbox is on If the circuit breaker has tripped determine the cause...

Страница 62: ...al If firebox door does not close tightly adjust using the appropriate procedure see Owner Serviceable Items Fig 80 NOTE If the outdoor furnace is operated with the door open the firebox door seal wil...

Страница 63: ...rete slab up to temperature the first time will take a considerable amount of time and wood once warm wood consumption will be reduced if the concrete slab and building are insulated properly The foll...

Страница 64: ...als are needed to optimize the operation of the outdoor furnace 7 Wood contains too much moisture Use correctly sized seasoned wood I CORROSION IS PRESENT Corrosion in the firebox can occur when the o...

Страница 65: ...plug from the unused supply port to prevent damage from water freezing 1 1 4 1 1 4 1 1 4 Drain Valve Plug NOTICE For use with aluminum or copper conductors p n 7000039 SECTION 6 GENERAL INFORMATION M...

Страница 66: ...64 E CLASSIC 1450 WIRING DIAGRAM Section 6 General Information...

Страница 67: ...65 Section 6 General Information E CLASSIC 1450 WIRING DIAGRAM OPTIONAL POWER IGNITION...

Страница 68: ...OOD Wood that has been dried to less than 25 moisture content and kept out of the weather to maintain that moisture content SECONDARY AIR CHARGE TUBE Tube located on the bottom of the firebox that pro...

Страница 69: ...67 NOTES...

Страница 70: ...68 NOTES...

Страница 71: ...69 NOTES...

Страница 72: ...r gaskets seals heat shields paint charge tube grates combustors aquastats actuators heat refractory and firebrick Parts that are factory installed by Central Boiler but are manufactured by others may...

Отзывы: