- 22 -
Back Position
: Normal operation after installation is complete, process or
manometer port is closed.
Front Position
: Storage or shipping operation, liquid or suction line connection
is closed.
Middle Position
: Installation operation, all ports are open for evacuation, charge
and manometer.
BACK POSITION FRONT POSITION MIDDLE POSITION
Fig. 12 ROTALOCK Valve Operation
BACK POSITION FRONT POSITION MIDDLE POSITION
Fig. 13 Base Valve Operation
5.
Checking Pressure Control Settings
1) Use of the
encapsulated pressure control (if applicable)
Fixed suction pressure setting: Cut in = 32 psig; Cut out = 10 psig