Fig. 14 Fixed Pressure Control
2)
Use of the adjustable pressure control (if applicable for pump-down)
Suction pressure setting: Cut out=5 psig; Cut in=25 psig; Differential=20 psig
Head pressure setting: Cut out=230 psig; Cut in=150 psig; Differential=80 psig
It may need to adjust the setting in the field to get the right cycle time.
A.
P70 Single/Dual Control
B.
PS2 Dual Control
Fig. 15 Adjustable Pressure Control