background image

 

 

25 

 

 

V9.14 

 

 

 

C o o l i n g   U n i t   R u n s   C o n s t a n t l y

 

Improper installation, inadequate insulation, or a cellar that is 
too large will cause the cooling unit to run continuously and 
cannot be troubleshooted. 

The cooling unit is designed to turn on when the air temperature in 
the  cellar  rises  ABOVE  the  Minimum  Set  Point  +  Temperature 
Differential,  and  turn  off  when  the  air  temperature  falls  below  the 
Minimum Set Point. For example, if the Minimum Set Point is 58°F and 
the Temperature Differential is 4°F, the cooling unit will turn on above 
62°F  and  turn  off  below  58°  F.  In  this  example,  the  average 
temperature  inside  the  cellar  will  be  60°F.  When  bottles  are  first 
loaded in the cellar, the cooling unit will run  continuously (even up 
to a week) until the temperature inside the cellar falls below the Set 
Point. 

CellarPro  6200  and  8200  Series  cooling  units  are  designed  to 
maintain  proper  wine  storage  temperatures  inside  cellars  with 
adequate insulation up to 2200 cubic feet, depending on the cooling 
unit, thermal load and desired cellar temperature. 

Hot  weather  conditions,  insufficient  ventilation  and/or  dirty  condenser 
filters  may  cause  the  cooling  unit  to  run  continuously.  To  reduce  cycle 
times, 

1.

 

Remove any obstructions to air flow to or from the unit 

2.

 

Check to make sure the condenser filter is clean 

3.

 

Increase the Fan speed to High 

4.

 

Increase the supply of cool air to the space outside the 
condenser coils, using a fan, ducting or an exhaust system to 
remove heat from the space. 

5.

 

Raise the Minimum Set Point on the cooling unit 

C o o l i n g   U n i t   I s   D r i p p i n g  

The  cooling  unit  is  designed  to  remove  excess moisture  from  inside the 
cellar, which collects in the drip pan of the cooling unit and is evaporated 
by the condensate heater. Excess moisture can occur when the cooling unit 
runs constantly, when the Minimum Set Point is too low and/or when the 
cellar doesn’t have a good seal from the outside environment. To eliminate 
overflow, do the following: 

IV. Troubleshooting 

Содержание 6200VSi

Страница 1: ...V9 14 Control the Elements Owner s Manual 6200VSi 6200VSx 8200VSi 8200VSx...

Страница 2: ...ave questions please don t hesitate to contact your dealer or CellarPro directly We can be reached during normal business hours at 1 877 726 8496 You also may contact us anytime via email at info cell...

Страница 3: ...3 V9 14 T a b l e o f C o n t e n t s I Specifications and Cut Sheets 4 II Installation Instructions 9 III Operating Instructions 15 IV Troubleshooting 25 V Limited Warranty 27...

Страница 4: ...Cut Sheet Model Dimensions inches W x D x H Weight Running Compressor Amps 6200 8200VSi 16 1 x 29 3 x 21 9 incl drain 130 10 5A 6200 11 8A 8200 6200 8200VSi 16 1 x 33 1 x 21 9 incl rear duct hood dra...

Страница 5: ...and the rear of the cooling unit require a minimum clearance of 8 inches These units also can be placed completely INSIDE or OUTSIDE the cellar when used in combination with our duct kits Ambient Env...

Страница 6: ...face mounted fixtures are recommended over recessed lighting which can allow air to leak into the cellar It is important that all walls joints doors and windows electrical outlets and or switches pipe...

Страница 7: ...he cooling unit to produce cold air In addition the cooling unit must be installed so that after its installation the condenser coils are accessible for periodic cleaning or replacing of the filter Th...

Страница 8: ...el kit that can be installed remotely up to 10 feet from the cooling unit either inside or outside the cellar and a bottle probe 10 foot cord that can be plugged into the cooling unit Power Requiremen...

Страница 9: ...note The cooling system is programmed with a 3 Minute Delay at Startup to protect its internal components Cut a hole in the wall that is 1 4 inch larger than the dimensions W x H of the cooling unit a...

Страница 10: ...ove the cooling unit which is very heavy Do not place the cooling unit on unprotected bottle racks Tilt the cooling unit slightly backwards The rear of the cooling unit should be slightly lower than t...

Страница 11: ...11 V9 14 6200 8200VS Installation Diagrams...

Страница 12: ...the side brackets there are no mounting holes for the bottom mounting bracket in the case of the cooling unit Secure the top and bottom brackets to the side brackets with 4 1 4 20x5 8 bolts and lockw...

Страница 13: ...sult the manufacturer for recommendations For duct runs greater than 50 equivalent feet the auxiliary fan option is required Ducted Installations Front Duct Kit 1 Ductwork must be attached to BOTH the...

Страница 14: ...determine the total equivalent feet of a specific duct routing design or consult the manufacturer for recommendations 5 The High fan speed setting is required for long duct runs and as ambient temper...

Страница 15: ...the time CellarPro cooling units are designed to maintain optimal temperatures for storing and aging fine wine CellarPro cooling units are not designed to maintain III Operating Instructions Summary K...

Страница 16: ...t Point For example if the Minimum Set Point is 58 F and the Temperature Differential is 4 F the cooling unit will turn on when the temperature rises above 62 F inside the cellar and it will turn off...

Страница 17: ...nd energy efficiency select the lowest fan speed that will maintain the desired cellar temperature High speed is recommended for initial cellar pull down extreme temperature conditions and ducted inst...

Страница 18: ...bottle probe sold separately to control the cellar by liquid temperature rather than air temperature inside the cellar Disconnecting the probe will automatically return the control to air temperature...

Страница 19: ...displayed RST will blink three times to indicate confirmation Set Button The cooling unit is factory preset with a Minimum Set Point of 58 F and a Temperature Differential of 4 This means that the co...

Страница 20: ...on when the cooling unit is in Energy Saver mode In Energy Saver mode the Minimum Set Point increases 4 F and the Temperature Differential is unchanged Quick Chill Button To activate the Quick Chill...

Страница 21: ...l the unit reaches set point This mode is useful after loading warm bottles in the cabinet The cooling unit has a factory default defrost cycle that initiates every 16 hours for 20 minutes When the co...

Страница 22: ...ng is 0 6 TEMPERATURE DIFFERENTIAL The factory preset for this setting is 4 This setting determines the Temperature Differential and therefore the temperature at which the cooling unit will cycle on T...

Страница 23: ...atures that are too hot The compressor and condenser fan will turn off until the condenser temperature falls below 120 F Maintenance The condenser coils at the back of the cooling unit will collect du...

Страница 24: ...et has dropped below the alarm temperature setting Call CellarPro at 877 726 8496 Check if the cellar has a leak Check if door was left open Lower the ambient temperatures Check for appropriate instal...

Страница 25: ...age temperatures inside cellars with adequate insulation up to 2200 cubic feet depending on the cooling unit thermal load and desired cellar temperature Hot weather conditions insufficient ventilation...

Страница 26: ...lso make sure that there aren t any obstructions to the intake and or exhaust vents If your wine cabinet has a grill remove the grill and or any other obstructions above top vent or behind back vent t...

Страница 27: ...ry or an authorized dealer Damage caused by others or by any cause beyond the control of CellarPro shall not be considered defects in material or workmanship and are not covered by the warranty The li...

Отзывы: