19
V9.14
Power “On” / “Off”
Press “Power” to turn the unit on and off.
When the “Compressor On” indicator light
is on, the Compressor is running.
When the “Fan On” indicator light is on, the
Fan is running.
Please note: The cooling system is
programmed with a
3 - Mi nu te D e l a y a t
S tar t u p
to protect internal components.
Up and Down Buttons
To view the “High Temp” recorded by the
cooling unit, press the “Up” button once.
To view the “Low Temp” recorded by the
cooling unit, press the “Down” button
once.
To reset the “High Temp” or “Low Temp”,
press the “Set” button for three seconds
while “Hi” or “Lo” is displayed. “RST” will
blink three times to indicate confirmation.
Set Button
The cooling unit is factory preset with a
Minimum Set Point of 58°F and a
Temperature Differential of 4°.
This means that the cooling unit will turn
on when the display rises above 62°F
(58°F + 4°F), and turn off when the
display falls below 58°F. In this example,
the average temperature inside the cellar
will be 60°F.
The cooling unit is factory preset with a
Minimum Set Point of 58°F and a
Temperature Differential of 4°F. This
means that the cooling unit will turn on
when the display rises above 6 2°F (58°F
+4°F), and turn off when the display falls
below 58°F. In this example, the average
temperature inside the cellar will be 60°F.
To view the Minimum Set Point, press the
“Set” button for one second.