
5
PARAMETER DEFINITIONS FOR SYSTEM SOFTWARE
1. Dispense Total
– This parameter indicates the total amount of water dispensed (in ounces or milliliters) for a mixing chamber. The
Dispense Total does not include Rinse Dispenses. The maximum Dispense Total value is 16,777,216 ounces; after which the value will
begin again from zero. This parameter cannot be reset to zero.
Default Values has no effect on this parameter.
2. Dispense Counter
– This parameter indicates the total number of cups dispensed for a selected Serving Size. The Dispense Counter does
not include Rinse Dispenses. The maximum Dispense Counter value is 49,999; after which the value will begin again from zero. In Service
Mode this parameter can be reset to zero by simultaneously depressing the
▼
and
▲
Keys.
Default Values has no effect on this
parameter.
3. Dispense Mode
– This parameter determines whether the system dispenses in a continuous (Free Flow) or fixed size (Portion Control)
method.
The default setting for this parameter is Portion Control.
4. Serving Size
– This parameter determines the amount of water dispensed for each Dispense Key when the Dispense Mode is set to Portion
Control.
The default setting is 8.0 ounces. The minimum Serving Size is 2.0 ounces. The maximum Serving Size is 64.0 ounces.
5. Gram Throw
– This parameter determines the ratio of product to water during a Dispense for a selected Hopper. The units of measure for
Gram Throw are proportional to Auger Turns per ounce of water. At a Fill Constant of 1.00 ounces per second the maximum Gram Throw is
100 and the minimum Gram Throw is 20. The maximum and minimum values are scaled proportional to a Fill Constant of 1.00 ounces per
second. For example: if the Fill Constant is set to 1.30 ounces per second the maximum Gram Throw would be (100*1.00)/1.3 = 77. This
prevents the user from requesting a Gram Throw that is beyond the capability of the Auger Motor. Auger Start and Stop Times have no
effect on this parameter.
The default setting for this parameter will reset all gram throw settings to factory specs.
6. Auger Start Time
– This parameter sets the time that the Auger starts to turn relative to the activation (opening) of the Dump Valve. A
positive value indicates an Auger starting at some time after the opening of the Dump Valve. A negative number indicates an Auger starting
at some time before the opening of the Dump Valve. The minimum Auger Start Time = (-3.0) seconds. The maximum Auger Start Time is
3.0 seconds.
The default value for this parameter is 0.3 seconds.
7. Mixer Start Time
– This parameter sets the time that the Mixer starts to turn relative to the activation (opening) of the Dump Valve. A
positive value indicates a Mixer starting at some time after the opening of the Dump Valve. A negative number indicates a Mixer starting at
some time before the opening of the Dump Valve. The minimum Mixer Start Time = (-3.0) seconds. The maximum Mixer Start Time is 3.0
seconds.
The default value for this parameter is 0.3 seconds.
8. Auger Stop Time
– This parameter sets the time that the Auger stops turning relative to the de-activation (closing) of the Dump Valve. A
positive value indicates an Auger stopping at some time after the closing of the Dump Valve. A negative number indicates an Auger stopping
at some time before the closing of the Dump Valve. The minimum Auger Stop Time = (-3.0) seconds. The maximum Auger Stop Time is 3.0
seconds.
The default value for this parameter is 0.3 seconds.
9. Mixer Stop Time
– This parameter sets the time that the Mixer stops turning relative to the de-activation (closing) of the Dump Valve. A
positive value indicates a Mixer stopping at some time after the closing of the Dump Valve. A negative number indicates a Mixer stopping at
some time before the closing of the Dump Valve. The minimum Mixer Stop Time = (-3.0) seconds. The maximum Mixer Stop Time is 3.0
seconds.
The default value for this parameter is 0.6 seconds.
10. Fill Constant
– This parameter must be set for each of the Dump Valves. The maximum Fill Constant is 1.5 oz/sec. The minimum Fill
Constant is 0.1 oz/sec. The maximum and minimum values are scaled proportional to a Gram Throw of 100. For example: if the highest
Gram Throw setting is 77 then the maximum Fill Constant would be (100*1.00)/77 = 1.30. This prevents the user from requesting a Gram
Throw that is beyond the capability of the Auger Motor.
The default settings for this parameter are 0.25 ounces per second for LEFT &
MIDDLE CHAMBER, and 1.00 oz/sec For RIGHT (Milk) CHAMBER.
11.
Rinse Dispense Time
– This parameter determines the amount of time that the Dump Valve is open during a Rinse Cycle. The minimum
Rinse Time = 3 seconds. The maximum Rinse Time is 15 seconds.
The default value for this parameter is 6 seconds.
12. Rinse Warning Status
– This parameter determines whether the Rinse Warning Option is turned ON or OFF. If this option is ON the
system generates a Rinse Warning if a Hopper has dispensed and has not been Rinsed for of time greater than that defined by (50 * Rinse
Lockout Time) minutes. For example: If the Rinse Warning Status is ON and the Rinse Lockout Time is 6 Hours then a Rinse Warning will
be generated when a Hopper is not Rinsed for more than (50 * 6 = 300) minutes (5 hours). Generating a Rinse Warning will cause the
audible alarm to sound for two seconds and the Rinse Warning Screen to be displayed for five seconds. The system will then revert back to
Содержание GB5MF-IT
Страница 1: ......
Страница 2: ......
Страница 5: ......
Страница 6: ......
Страница 23: ......
Страница 24: ......
Страница 25: ......
Страница 26: ......
Страница 27: ......
Страница 28: ......
Страница 29: ...P N DESCRIPTION QTY 23...
Страница 30: ......
Страница 32: ...DISPLAY LIGHT...
Страница 33: ......