11
8 Status display and
fault display
8.1 Status display
The status display is located on
Line 2 in the main screen (see
Table 2).
If a status with a lower priority
is being displayed and a status
with a higher priority occurs,
the newer status with the higher
priority will be displayed.
If this new higher status drops
out again, the old, lower status
will be displayed.
By default, the status with the
highest priority will be dis-
played. If there are additional
status messages, you can dis-
play
them in the submenu by press-
ing the ENTER key.
As soon as no more status
messages are pending, “Opera-
tion” is displayed.
The status of a previously se-
lected device is displayed in
Line 2 of the Device info menu
according to the same priority.
8.2 Fault display
The fault is located on Line 3 in
the main screen (see Table 3).
The fault of a previously se-
lected device is displayed in
Line 3 of the Device info menu
according to the same priority.
8.2.1 Sum failure
A sum failure is present if more
than one fault error is present
at the same time.
Sum failure =
more than one fault
Faults for generating the group
fault:
Battery interrupted
Battery voltage too high
Isol., charging module or
booster failure 1
Isol., charging module or
booster failure 2
Isol. failure
Communication failure
Luminaire failure
Minimum duration
8.2.1.1 Example of a sum
fault message
A sum fault is displayed if a
fault is present, for example
“Battery voltage too high” and
an “Isol., charging module or
booster failure 1” is present.
8.2.1.2 Example of no sum
failure message
If a “Battery voltage too high”
fault is present, no group fault
is displayed.
8.2.2
Display of additional
faults in the “Info device”
menu
By default, the fault with the
highest priority is displayed. If
there are additional fault mes-
sages, you can display them
in the submenu by pressing the
ENTER key.