Power factor / THD
> 99% / < 3%
Frequency range (selectable) / synchronization range
60 Hz (range 57 – 63 Hz) / 50 Hz (range 47 – 53 Hz)
DC Input Data
DC voltage: Nominal / range
48 Vdc / (40-60V)*
Nominal current (at 48 Vdc and 800 W output)
18.5 A
Maximum input current (for 15 second) / voltage ripple
22.5 A / < 10 mV RMS
AC Output Data
Efficiency AC to AC (EPC) / DC to AC
95% / >92%
Nominal voltage AC** (Adjustable)
120 V (100 - 130 Vac)
Frequency / frequency accuracy
60 or 50 Hz / 0.03%
Nominal Output power (VA) / (W)
1000 VA / 800 W
Short time overload capacity
125% (15 seconds)
Admissible load power factor
Full power rating from 0 inductive to 0 capacitive
Total harmonic distortion (resistive load)
< 3%
Load impact recovery time (10% - 90%)
≤ 0.4 ms
Nominal current
8.3 A @ 120 Vac
Crest factor at nominal power
3 : 1 for load P.F. ≤ 0.7
Short circuit clear up capacity 0-20 ms
34 A
Short circuit current after 20 ms
16.5 A for 15 s, 12.5 A from 15 to 60 s, after 60 s -
manual reset is required
AC output voltage stability
±1% from 10% to 100% load
Signaling & Supervision
Display
Synoptic LED
Supervision / Part number
Inview S Slot - T602004110 and Inview S -
T302004100
Remote on / off
On rear terminal of the shelf through Inview
Safety & EMC
Safety
UL1778
EMC
EN 61000-4-2 / EN 61000-4-3 / EN 61000-4-4 / EN
61000-4-5 / EN 61000-4-6 / EN 61000-4-8 ETSI EN
300386 v1.9.1 / FCCpart 15 class A
* Permanent 800 W / derating apply based on internal heatsink T°.
** Operation within lower voltage networks leads to de-rating of power performances.
Building Blocks
14
- Bravo 10 - 48/120 - User manual - v1.1