13: Maximum charger current setting
Interface
Setting
Parameter 2:
Set up the charger maximum current.
For low voltage model with 24/36/48VDC
1/2/4/6/8:
setting the charger maximum current 1/2/4/6/8
in Ampere. (Default: 2A)
For high voltage model with 24/36/48VDC
1/2/4/6/8/10/12:
setting the charger maximum current
1/2/4/6/8/10/12 in Ampere. (Default: 2A)
For low voltage and high voltage model with 72/96VDC
1/2/4/6/8:
setting the charger maximum current 1/2/4/6/8
in Ampere. (Default: 2A)
Note: Please set the appropriatecharger current based on
battery capacity used. The recommended charging current is
0.1C~0.3C of battery capacity as following table for
reference.
Battery capacity (AH) Total charging current (A)
7-20
2
20-40
4
40-60
6
60-80
8
80-100
10
100-150
12
14: Charger boost voltaje setting
Interface
Setting
Parameter 2:
Set up the charger boost voltage.
2.25-2.40:
setting the charger boost voltage from 2.25
V/cell to 2.40V/cell. (Default: 2.36V/cell)
15: Charger float voltaje setting
Interface
Setting
Parameter 2:
Set up the charger float voltage.
2.20-2.33:
setting the charger float voltage from 2.20
V/cell to 2.33V/cell. (Default: 2.28V/cell)