2-4. Setup the UPS
Before installing the UPS, please read below to select proper location to install UPS.
1.
UPS should be placed on the flat and clean surface. Place it in an area away from
vibration, dust, humidity, high temperature, flammable liquids, gases, corrosive and
conductive contaminants. For options outdoor please consult our local office. Install
the UPS indoors in a clean environment, where it is away from window and door.
Maintain minimum clearance of 100mm in the bottom of the UPS to avoid dust and
high temperature.
2.
Maintain an ambient temperature range of 0ºC to 45ºC for UPS optimal
operation. For every 5ºC above 45ºC, the UPS will derate 12% of nominal capacity
at full load. The highest working temperature requirement for UPS operation is 60ºC.
3.
It’s required to maintain maximum altitude of 1000m to keep UPS normal operation
at full load UPS. If it’s used in high altitude area, please reduce connected load.
Altitude derating power with connected loads for UPS normal operation is listed as
below:
4. Place UPS: It’s equipped with fan for cooling. Therefore, place the UPS in a well-
ventilated area. It’s required to maintain minimum clearance of 100mm in the front
of the UPS and 300mm in the back and two sides of the UPS for heat dissipation
and easy- maintenance.
5.Connect to External Battery Pack