07: Bypass voltaje range setting
Interface
Setting
Parameter 2:
Set the acceptable high voltage point and
acceptable low voltage point for Bypass mode by pressing the
Down key or Up key.
HLS:
Bypass high voltage point
For 200/208/220/230/240 VAC models:
230-264:
setting the high voltage point in parameter 3 from
230Vac to 264Vac. (Default: 264Vac)
For 100/110/115/120/127 VAC models:
120-140:
setting the high voltage point in parameter 3 from
120Vac to 140Vac. (Default: 132Vac)
LLS:
Bypass low voltage point
For 200/208/220/230/240 VAC models:
170-220:
setting the low voltage point in parameter 3 from
170Vac to 220Vac. (Default: 170Vac)
For 100/110/115/120/127 VAC models:
85-115:
setting the low voltage point in parameter 3 from
85Vac to 115Vac. (Default: 85Vac)
08: Bypass frequency range setting
Interface
Setting
Parameter 2:
Set the acceptable high frequency point and
acceptable low frequency point for Bypass mode by pressing
the Down key or Up key.
HLS:
Bypass high frequency point
For 50Hz output frequency models:
51-55Hz:
setting the frequency high loss point from 51Hz to
55HZ(Default: 53.0Hz)
For 60Hz output frequency models:
61-65Hz:
setting the frequency high loss point from 61Hz to
65Hz(Default: 63.0Hz)
LLS:
Bypass low Frequency point
For 50Hz output frequency models:
45-49Hz:
setting the frequency low loss point from 45Hz to
49HZ(Default: 47.0Hz)
For 60Hz output frequency models:
55-59Hz:
setting the frequency low loss point from 55Hz to
59Hz(Default: 57.0Hz)