background image

User’s Manual 

CD-KP for CD3000E & Multidrive 

C.D. Automation Srl 

 

 

19 

www.cdautomation.com 

 

2.8 Configuration menu (

Conf

 
In this menu is possible to configure CD-KP. The scrolling through the parameters is done by 
pressing the roll key 

. To modify parameters’ values press up 

 or down 

 keys. When a 

parameter is being modified, its value will flash. To confirm and save the new value, press the 
L/R 

L

R

 key. 

 
To return to main menu, press together  the roll 

 and up 

 keys. 

 

2.8.1 Unit’s address (

Id.Un

Address of the thyristor unit connected with CD-KP. 
Possible values: 

1

 – 

255

 

CD-KP (Master device) can connect with just one slave device located at address specified by 
this parameter. The communications between CD-KP and thyristor unit is on serial link RS485 
with MODBUS protocol. 
 

2.8.2 Retransmission (

retr.

Retransmission parameter’s selection. 
Possible values: 

off

 , 

P 4

 , 

P 8

 , 

P31

 , 

P32

 , 

P33

 , 

P34

 

CD-KP can read from the connected thyristor unit one of the above parameters and to 
retransmit it on analog output in voltage (0÷10V) or current (4÷20mA or 0÷20mA). 
More informations about thyristor unit’s parameters can be found on CD3000E and Multidrive 
manuals. 
 

2.8.3 Retransmission type (

t.ret

Retransmission type’s selection. 
Possible values: 

0- 10

 , 

0- 20

 , 

4- 20

 

Retransmission type’s selection: 0÷10V, 0÷20mA, 4÷20mA. 

 
Warning: 

this selection must be compatible with hardware selection done via link jumper (see 

retransmission selection paragraph). 

 

2.8.4 Baud rate (

baud

Communication speed’s selection. 
Possible values: 

4.8

 , 

9.6

 , 

19.2

 

The communication speed can be set at 4800, 9600 or 19200 Bps. 
 

Warning: 

be sure that CD-KP and thyristor unit have the same communication speed. 

 

2.8.5 L/R key (

bt.Lr

L/R 

L

R

 key function. 

Possible values: 

off

 , 

On

 

When in remote mode, the thyristor unit is driven by its remote reference. When in local 
mode, the thyristor unit is driven by CD-KP using the up 

 and down 

 keys. 

 

2.8.6 Command sub-menu (

sh.Co

Enable/disable of command sub-menu in operator menu. 
Possible values: 

off

 , 

On

 

 

Содержание CD3000E

Страница 1: ...ER MANUAL Rev 02 2005 CD KP for MULTIDRIVE CD3000E CD Automation S r l Via Picasso 34 36 20025 Legnano MI Italy Tel 39 0331 577479 Fax 39 0331 579479 e mail info cdautomation com web www cdautomation com ...

Страница 2: ......

Страница 3: ...lection 6 1 6 Frontal Keypad 7 1 7 Frontal plug in connector 7 1 8 Default settings 8 1 9 Start up 8 2 Menu general description 9 2 1 General description of menus 9 2 2 Password usage 9 2 3 Operator menu oper 12 2 4 Command menu Cnd 14 2 5 Calibration menu CAL 14 2 6 Diagnostic menu dIA 15 2 7 Setup menu SEtU 17 2 8 Configuration menu Conf 19 2 9 Restoring of default configuration 21 ...

Страница 4: ...rameters by unauthorised personnel CD KP has an isolated analog output 0 10V 0 20mA 4 20mA to retransmit parameters value as voltage power and reference Working temperature 0 45 C HR 90 Supply votage 115 230 Vac 10 50 60 Hz Power drain 3VA Display 1 LED 7 segments 10mm Display 2 LED 7 segments 8mm Display 3 LED 7 segments 10mm Units featured CD KP can communicate with CD3000E or Multidrive units v...

Страница 5: ...User s Manual CD KP for CD3000E Multidrive C D Automation Srl 5 www cdautomation com 1 3 Dimensions 48 96 ...

Страница 6: ...r 240Vac selectable A B 1 5 Retransmission selection In configuration menu it is possible to select which variable to retransmit and the output type 0 20mA 4 20mA 0 10V There is also an hardware configuration that must be done a jumper must be set near the rear terminals as showed in figures on the right If the output is configured as 0 20mA or 4 20mA the jumper must be set as in fig A current sel...

Страница 7: ...ash and the control on serial link will be released In this condition no operation is possible on CDKP and all keys are disabled Unplugging the configuration cable the CD KP will return in its normal working condition Error Alarm display E communication error A Multidrive CD3000E alarm Roll key Used to scroll the items in menus or to confirm a selection Upper display Used to display the menu items...

Страница 8: ...units at address 1 and baud rate 19200 The variables displayed in operator menu are average power P32 average current Arst parameter voltage and reference signal in percentage All the menus are protected by password with value 255 1 9 Start up Before to supply the CD KP check that the wiring is correct and verify the supply line voltage value 120Vac or 240Vac Automatically the operator menu 1 will...

Страница 9: ...es access to the selected section All the sections except the oper section are usually protected by password to avoid access by unauthorised personnel The password policy can be changed in configuration menu Conf 2 2 Password usage When the user tries to enter in a protected menu the CD KP will ask for a password Insert the password using the up and down keys and confirm with roll key 0 Wrong pass...

Страница 10: ...C D Automation Srl CD KP for CD3000E Multidrive User s Manual www cdautomation com 10 Cnd CaL Dia oPEr 0 Cnd Cnd 0 0 7 P 51 P Wrong password OP 1 OP 2 OP 3 Cnd Cnd Cnd Wrong password Wrong password ...

Страница 11: ...idrive C D Automation Srl 11 www cdautomation com 0 23 P P113 Setu Conf 0 1 oFF 0 10 19 2 P 32 oFF oFF P 8 Arst P 8 P 8 P 31 0 0 0 0 0 0 Wrong password L R L R L R L R L R L R L R L R L R L R L R L R L R L R L R L R L R L R Wrong password ...

Страница 12: ...see parameter 008 on CD3000E or Multidrive manual The user can choose the parameters displayed in OP2 sub menu by changing this setting in configuration menu Conf 2 3 3 OP3 sub menu By default in this sub menu are displayed the voltage to the load upper display and the reference lower display The voltage is expressed in volts see parameter 031 on CD3000E or Multidrive manual The external reference...

Страница 13: ...thers by pressing the up and down keys Warning the alarm s displaying sequence doesn t respect the alarm s event time 2 3 6 Local remote mode CD KP can switch between local and remote mode only when the user is in OP1 OP2 or OP3 menu Pressing once the L R L R key CD KP switch in local mode and a L will flash in lower display At this moment the operator can use the up and down keys to give a refere...

Страница 14: ...ether the roll and up keys 2 5 Calibration menu CAL In this menu is possible to display and modify the parameters 116 operative voltage and 119 nominal current of the load and to execute the automatic heater break alarm calibration The parameter 116 will appear in upper display u400 the parameter 119 will appear in lower display n88 6 The roll key will choose wich parameter to modify flashing lett...

Страница 15: ... percentage value of reference signal on terminals 17 18 on terminal block L2 of Multidrive or terminals 7 8 on terminal block LB1 of CD3000E 2 6 3 Parameter 10 Current limit P 10 This parameter displays the percentage value of reference signal on terminals 21 22 on terminal block L2 of Multidrive or terminals 7 10 on terminal block LB1 of CD3000E 2 6 4 Parameter 48 Digital inputs P 48 This parame...

Страница 16: ... 0 no output active 0 no output active 1 configurable output 2 active 1 line activation signal 2 alarm signal 4 configurable output 1 active Example if parameter 48 displays 03 it means no output active AND line activation signal alarm signal 2 6 6 Parameter 51 Current limit enabling P 51 This parameter displays the current limit s status P 51 0 à the current limit is disabled P 51 1 à the current...

Страница 17: ...ing mode selection P 23 0 Burst firing 1 Phase angle 2 Delayed triggering Burst firing 2 7 2 Parameter 24 Ramp up P 24 0 4095 x 0 7 sec 2 7 3 Parameter 25 Ramp down P 25 0 4095 x 0 7 sec 2 7 4 Parameter 66 HB sensitivity P 66 0 100 2 7 5 Parameter 68 HB enabled disabled P 68 0 9999 2 7 6 Parameter 70 Feed back selection P 70 0 Current I rms 1 Voltage V rms 2 Power VxI 3 External 2 7 7 Parameter 83...

Страница 18: ... 4095 2 7 13 Parameter 106 Analog output 2 rescaling P106 Span for external indicator 1 4095 2 7 14 Parameter 108 Analog output 3 rescaling P108 Span for external indicator 1 4095 2 7 15 Parameter 110 Analog output 4 rescaling P110 Span for external indicator 1 4095 2 7 16 Parameter 112 Digital output 2 configuration P112 0 Current limit 1 Heater Break 2 Unbalanced load 2 7 17 Parameter 113 Digita...

Страница 19: ... read from the connected thyristor unit one of the above parameters and to retransmit it on analog output in voltage 0 10V or current 4 20mA or 0 20mA More informations about thyristor unit s parameters can be found on CD3000E and Multidrive manuals 2 8 3 Retransmission type t ret Retransmission type s selection Possible values 0 10 0 20 4 20 Retransmission type s selection 0 10V 0 20mA 4 20mA War...

Страница 20: ...es P 4 P 8 P10 P11 P31 P32 P33 P34 P35 arst More informations about thyristor unit s parameters can be found on CD3000E and Multidrive manuals 2 8 10 OP2 lower display op2L Displayed parameter in lower display of OP2 menu Possible values P 4 P 8 P10 P11 P31 P32 P33 P34 P35 arst More informations about thyristor unit s parameters can be found on CD3000E and Multidrive manuals 2 8 11 OP3 upper displ...

Страница 21: ... password for calibration menu but referred to setup menu 2 8 16 Configuration menu password P Con Protection password for configuration menu Possible values 0 255 As password for calibration menu but referred to configuration menu 2 8 17 Command menu password P Cnd Protection password for command menu Possible values 0 255 As password for calibration menu but referred to command menu 2 8 18 Off l...

Отзывы: