User’s Manual
CD-KP for CD3000E & Multidrive
C.D. Automation Srl
17
www.cdautomation.com
2.7 Setup menu (
SEtU
)
This menu is similar to diagnostic menu. The scrolling through the parameters is done by
pressing the roll key
. To modify parameters’ values press up
or down
keys.
All the parameters showed in this menu are stored in CD3000E or Multidrive eeprom, more
informations can be found on thyristor units manuals.
To return to main menu, press together the roll
and up
keys.
2.7.1 Parameter 23 – Firing mode selection (
P 23
)
0
Burst firing
1
Phase angle
2
Delayed trig Burst firing
2.7.2 Parameter 24 – Ramp up (
P 24
)
0 – 4095
x 0,7 sec.
2.7.3 Parameter 25 – Ramp down (
P 25
)
0 – 4095
x 0,7 sec.
2.7.4 Parameter 66 – HB sensitivity (
P 66
)
0 – 100%
2.7.5 Parameter 68 – HB enabled/disabled(
P 68
)
0 – 9999
2.7.6 Parameter 70 – Feed back selection (
P 70
)
0
Current I (rms)
1
Voltage V (rms)
2
Power VxI
3
External
2.7.7 Parameter 83 – Burst Firing setting (
P 83
)
1 – 256
2.7.8 Parameter 84 – Ramp setting in Burst Firing (
P 84
)
Parameter available only with Multidrive 3PH
1 – 100
2.7.9 Parameter 85 – Delay triggering (
P 85
)
Parameter available only with Multidrive 2PH
1 – 100
2.7.10 Parameter 91 – Internal current limit value (
P 91
)
1 – 100