4.0 Operation 

This section describes the steps necessary to install and remove the circuit breaker using the RRS-2-BE.   

 
4.1 Circuit Breaker Installation 

These are the following requirements and steps for circuit breaker installation using the RRS-2-BE. 
 

4.1.1 Requirements for Installation 

The following installation procedure assumes that the following prerequisites have been met: 
 

1.

 

The circuit breaker racking mechanism is in working order. 

2.

 

The circuit breaker has been properly maintained. 

3.

 

The circuit breaker is removed from  the cubicle  and OPEN

  according to 

manufacturer specifications.

 

4.

 

The tooling is connected properly to both the circuit breaker and the RRS-2-BE. 
 

DANGER! 

*For your safety please ensure that all personnel follow the personal protective 
equipment rules and regulations along with following all of the manufacturer guidelines 
at ALL times. 

 

DANGER! 

*Remove control power from the control circuit if applicable in order to prevent the 
accidental closing or tripping of the breaker during the racking procedure. 

 

4.1.2 Steps for Installation 

To install the circuit breaker to the OPERATING position, perform the following steps. 
 

1.

 

Ensure the RRS-2-BE is properly setup and attached to the breaker using the breaker 
specific tooling provided. 

 
2.

 

Verify the circuit breaker is OPEN  according to manufacturer specifications and 
company safety policies. 

 

3.

 

Exit the arc flash boundary with the pendant station. 

 

4.

 

Ensure the emergency stop push button is deactivated by turning the button 
clockwise to unlatch. 

 
5.

 

Use the pendant station as is discussed in the given RRS-2-BE tooling guide to install 
the breaker.  If the pendant  retractile cord is not long enough for the operator to 
leave the arc flash boundary additional pendant extension cords are available and 
the pendant station and pendant retractile cord can be replaced with an optional 
radio remote system. 

 

6.

 

Detach and uninstall the RRS-2-BE unit from the circuit breaker cubicle.

 

 

Содержание ArcSafe RRS-2-BE

Страница 1: ...RRS 2 BE Technical Manual P O Box 550 Argyle TX 76226 940 382 4411 www CBS ArcSafe com Remote Racking System CBS ArcSafe...

Страница 2: ...particular attention to DANGER Ensure that personnel using this equipment are adequately trained in the operation of the switchgear they are planning to work with that they are correctly stationed out...

Страница 3: ...ator positioned safely outside of the arc flash boundary The RRS 2 is powered from either standard AC power or the internal battery The RRS 2 BE is operated with the RSO BE via a radio The pendant sta...

Страница 4: ...3 5 Setting up the RRS 2 BE for Operation This section lists the preliminary steps for operation 3 3 Charging the RRS 2 BE This section describes the procedure for charging the remote racking system...

Страница 5: ...per training 1 Remove the cardboard cover by cutting the perimeter at the base with a utility knife or removing the nails screws 2 Carefully remove the steel strapping that secures the remote rack to...

Страница 6: ...s on while plugged in and charging 3 While charging feel free to use the RRS 2 BE in normal operation mode 4 Whenever possible leave the CBS ArcSafe RRS 2 BE plugged in and properly stowed with either...

Страница 7: ...crewdriver 1 Loosen the two screws with a Philips head screwdriver 2 Position the limit switches as desired these switches determine how the actuator extends and retracts 3 Secure the limit switches b...

Страница 8: ...mote racking system in front of the circuit breaker to be racked with the cubicle brace aligned with the circuit breaker cubicle 4 Ensure the safety shut off switch on the pendant station is off 5 Tur...

Страница 9: ...circuit in order to prevent the accidental closing or tripping of the breaker during the racking procedure 4 1 2 Steps for Installation Removal To install the circuit breaker to the OPERATING position...

Страница 10: ...c mode if possible 6 Detach and uninstall the RRS 1 unit from the circuit breaker cubicle as follows a Depress the emergency stop button rewind the pendant station cord and return the remote to the st...

Страница 11: ...ove control power from the control circuit if applicable in order to prevent the accidental closing or tripping of the breaker during the racking procedure 4 1 2 Steps for Installation To install the...

Страница 12: ...breaker specific tooling provided 2 Verify the circuit breaker is OPEN according to manufacturer specifications and company safety policies 3 Exit the arc flash boundary with the pendant station DANG...

Страница 13: ...s no abnormal noise or vibration If abnormal condition exists do not use 5 3 After Use After use clean the RRS 2 BE ensuring the unit is free of dust and debris Ensure the unit is free of oil or greas...

Страница 14: ...6 0 Ordering Replacement Parts When ordering replacement parts please specify the serial number and MFD from the RRS 2 BE nameplate From the RRS 2 nameplate Nomenclature RRS 2 BE Serial number MFD...

Страница 15: ...Remote Racking Unit RRS 2 BE Parts List Item Description CBS ArcSafe Part Image 1 Battery Charger 2 Power Cable 3 Male Power Connector 4 Mounted Female Power Adapter...

Страница 16: ...Remote Racking Unit RRS 2 BE Parts List Cont Item Description CBS ArcSafe Part Image 5 Power Switch 6 PS R6 C Radio Remote 7 RSO Case w Components 8 Standard Tires 9 Pneumatic Tires...

Страница 17: ...Remote Racking Unit RRS 2 BE Parts List Cont Item Description CBS ArcSafe Part Image 10 Front Wheel 11 Magnet Brace...

Страница 18: ...with the system that it came with Also to limit interference please ensure that the channel numbers of units purchased at different dates differ Radio Remote Receiver The radio remote receiver receive...

Страница 19: ...position past the on positions to the start position and then releasing the switch letting it spring back to the on position 3 0 Pendant Station Button Configurations ATTENTION The power on the system...

Страница 20: ...protective equipment PPE Guarantee Equipment is guaranteed free of inherent electrical or mechanical defects for one 1 year from date of shipment and to perform according to ratings under normal cond...

Страница 21: ...form as soon as possible Date CBS ArcSafe Model CIRCLE ONE RRS 2 RRS 2 BE CBS ArcSafe Serial Number Company Address 1 Address 2 City State Province Zip Postal Code Country Telephone and Fax Contact Pe...

Отзывы: