RSA-112Installation and Operation

1

1 Installation

D

ANGER

!

Before servicing any breaker, make sure that it matches the breaker discussed. If the breaker
does not match the breaker described above, please call CBS ArcSafe® for more information.

A

TTENTION

!

The location of certain items such as mimic bus, stickers, and/or placards may interfere with

the proper installation of the RSA. Please remove or re-position these items before installing

the RSA.

1. Ensure that the breaker to be operated is free from obstructions that may interfere with proper

installation of the RSA

2. If your breaker handle travels 135° or more, position the breaker’s charging handle to its lower left

position, as shown on the left, by pulling the handle out and rotating it counter-clockwise until just
before vertical then push the handle in to activate the stop.

If your breaker handle only travels 90°, position the handle to the upper left position, as shown on

the right.

The handle adapter on the RSA can be manually rotated to match the breaker handle position as
needed. The switch-gear handle and the RSA’s handle adapter must both touch the counter-

clockwise stop before operations can be performed.

Содержание RSA-112

Страница 1: ...nted in the United States of America Reproduction adaptation or translation without prior written permission is prohibited except as is allowed by law RSA 112 Installation and Operation 2616 Sirius Ro...

Страница 2: ...y install and remove a particular type of circuit breaker safely while stationed safely outside of the arc flash boundary during the potentially dangerous operation The lightweight and compact design...

Страница 3: ...is free from obstructions that may interfere with proper installation of the RSA 2 If your breaker handle travels 135 or more position the breaker s charging handle to its lower left position as shown...

Страница 4: ...tors shown below are fully seated against the switch gear and around the breaker as indicated 4 Ensure the button actuators are positioned properly over the Close and Trip buttons on the front of the...

Страница 5: ...RSA 112Installation and Operation 3...

Страница 6: ...ese settings will be found on a placard on the RSA For more information on programming the RSO IIID please refer to the RSO IIID Technical Manual 5 NOTE Depending on the breaker model the travel dista...

Страница 7: ...breakers come from the factory a variety of charging arm configurations As such the RSA can be configured to accommodate these variations Before Making Travel Adjustments Note that the RSA comes from...

Страница 8: ...ing a stopwatch or other timer press and hold the JOG button and record the time in seconds it takes the motor arm reach the upper hard travel stop This will be the new T1 and T2 setting on the RSO II...

Страница 9: ...3 2 Close Solenoid Adjustment 11 Loosen the bolt on the bottom of the right solenoid arm as indicated below 12 Slide or rotate the arm as required to align the close solenoid to the close button as in...

Страница 10: ...oid Adjustment 14 Loosen the bolt on the bottom of the left solenoid arm as indicated below 15 Slide or rotate the arm as required to align the close solenoid to the close lever without contacting the...

Страница 11: ...RSA 112Installation and Operation 9 Notes...

Страница 12: ...hat they are correctly stationed outside the arc flash boundary and that they comply with all applicable Federal State Local and In house safety regulations and procedures Attention should be given to...

Отзывы: