RSA-112Installation and Operation
1
1 Installation
D
ANGER
!
Before servicing any breaker, make sure that it matches the breaker discussed. If the breaker
does not match the breaker described above, please call CBS ArcSafe® for more information.
A
TTENTION
!
The location of certain items such as mimic bus, stickers, and/or placards may interfere with
the proper installation of the RSA. Please remove or re-position these items before installing
the RSA.
1. Ensure that the breaker to be operated is free from obstructions that may interfere with proper
installation of the RSA
2. If your breaker handle travels 135° or more, position the breaker’s charging handle to its lower left
position, as shown on the left, by pulling the handle out and rotating it counter-clockwise until just
before vertical then push the handle in to activate the stop.
If your breaker handle only travels 90°, position the handle to the upper left position, as shown on
the right.
The handle adapter on the RSA can be manually rotated to match the breaker handle position as
needed. The switch-gear handle and the RSA’s handle adapter must both touch the counter-
clockwise stop before operations can be performed.
Содержание RSA-112
Страница 5: ...RSA 112Installation and Operation 3...
Страница 11: ...RSA 112Installation and Operation 9 Notes...