RSA-112Installation and Operation
4
2 Operation
A
TTENTION
!
Please ensure that all cables are clear of moving parts. Failure to do so may result in damage
to cables and/or actuator.
A
TTENTION
!
Please ensure that the batteries to the RSO-IIID are fully charged or that the unit is plugged
into AC power.
For detailed instructions on the operation of the RSO-IIID please see the RSO-IIID Manual.
1. Ensure that the RSA is properly installed. See the Installation
Section for detailed instructions.
2. Connect the cables from the RSO-IIID to the RSA.
3. Turn the power switch on the RSO-IIID to the ON position.
4. Program the settings for the RSA into the RSO-IIID, if applicable.
These settings will be found on a placard on the RSA. For more
information on programming the RSO-IIID please refer to the
RSO-IIID Technical Manual.
5. NOTE: Depending on the breaker model, the travel distance on
the charging arm may be different than the factory settings. See
the Adjustments section for instructions to reset the travel stops
and travel times on the RSA if needed.
6. Ensure that the Auto-Retract (AR) function is set according to the
instructions on the setting placard on the RSA. For detailed
information on the AR function see the RSO-IIID instruction
manual
6. Exit the arc flash boundary
7. Once the timers have been properly set press the
CHARGE/CLOSE button to actuate the switch arm and charge
the breaker mechanism.
8. Press the CLOSE button to close the breaker.
9. Press the TRIP button to trip the breaker.
10. Remove the RSA when operation is complete
Содержание RSA-112
Страница 5: ...RSA 112Installation and Operation 3...
Страница 11: ...RSA 112Installation and Operation 9 Notes...